| 2020-10-29 10:07:53 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 2010803 |
| | 10/29/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A-0.1 & P1: PROVIDE PLUMBING FIXTURE |
| | CALCULATIONS IN ACCORDANCE WITH TABLE 403.3. PROVIDE A |
| | SCHEDULE ON THE PLAN THAT SHOWS THE NUMBER OF REQUIRED |
| | AND PROVIDED FIXTURES FOR EACH NEW OCCUPANCY. |
| | |
| | 2) A-0.1: PLEASE INCLUDE THE WATER HEATER COMPLIANCE |
| | DATA IN THE COMCHECK ENERGY REPORT- TABLE C404.2 FBC |
| | EC. |
| | |
| | 3) A-5: SHOW THE TURNING CIRCLE DIAMETERS IN THE TOILET |
| | ROOMS- SECTION 304.3 FBC ACC. |
| | |
| | 4) A-5: SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE |
| | FOR A FORWARD WHEELCHAIR APPROACH TO THE WHEELCHAIR |
| | ACCESSIBLE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW |
| | HOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN |
| | COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS. |
| | |
| | 5) A-5: PROVIDE AN ELEVATION DETAIL FOR THE DRINKING |
| | FOUNTAIN FOR STANDING PERSON USE SHOWING SPOUT HEIGHT |
| | AND SPOUT LOCATION- SECTION 602.7 FBC ACC. |
| | |
| | 6) P1 & P2: PROVIDE A WATER RISER DRAWING- SECTION |
| | 107.3.5.1.3 WPB. |
| | |
| | 7) P1 & P2: TWO NEW TENANT OCCUPANCIES ARE SHOWN. SHOW |
| | THE LOCATIONS OF THE NEW WATER METERS AND MAIN SHUTOFF |
| | VALVES TO THE SPACES- SECTIONS 605.1 & 606.1 FBC P. |
| | |
| | 8) P1 & P2: INDICATE HOW TEMPERED WATER WILL BE |
| | PROVIDED AT THE LAVATORY PER SECTION 416.5. PLEASE NOTE |
| | THAT TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER |
| | TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070- |
| | SECTION 607.1.2 FBC P. |
| | |
| | 9) P1 & P2: SHOW THE LOCATIONS OF WATER HAMMER |
| | ARRESTORS FOR SUPPLY LINES TO QUICK CLOSING VALVES- |
| | SECTION- 604.9 FBC P. |
| | |
| | 10) P2: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| | HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC. |
| | |
| | 11) P2, BAY 1B ISO: THE MOP SINK (P3) MUST BE |
| | INDIVIDUALLY VENTED BECAUSE IT CANNOT BE PART OF THE |
| | TOILET ROOM HORIZONTAL WET SYSTEM- SECTION 912.1 FBC P. |
| | |
| | 12) P2, BAY 12 ISO: THE LAVATORY IS MISLABELED (P1) |
| | INSTEAD OF (P2). |
| | |
| | 13) P2: SHOW THE TYPE AND SIZE OF HOT WATER PIPE |
| | INSULATION- TABLE C403.2.10 FBC EC. |
| | |
| | 14) INDICATE THE TYPE OF WALL FINISHES TO BE INSTALLED |
| | IN THE RESTROOMS AND AT THE MOP SINK LOCATIONS IN |
| | ACCORDANCE WITH SECTION 310.3 FBC P, AND 1210.2.2 FBC |
| | B. |
| | |
| | 15) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION |
| | 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |