2020-10-29 10:07:531ST REVIEW FBC-2017 PLUMBING
 PERMIT- 2010803
 10/29/2020
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS A-0.1 & P1: PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.3. PROVIDE A
 SCHEDULE ON THE PLAN THAT SHOWS THE NUMBER OF REQUIRED
 AND PROVIDED FIXTURES FOR EACH NEW OCCUPANCY.
  
 2) A-0.1: PLEASE INCLUDE THE WATER HEATER COMPLIANCE
 DATA IN THE COMCHECK ENERGY REPORT- TABLE C404.2 FBC
 EC.
  
 3) A-5: SHOW THE TURNING CIRCLE DIAMETERS IN THE TOILET
 ROOMS- SECTION 304.3 FBC ACC.
  
 4) A-5: SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE
 FOR A FORWARD WHEELCHAIR APPROACH TO THE WHEELCHAIR
 ACCESSIBLE FOUNTAIN- SECTION 602.2 FBC ACC, AND SHOW
 HOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN
 COMPLIANCE WITH SECTION 307.2 PROTRUSION LIMITS.
  
 5) A-5: PROVIDE AN ELEVATION DETAIL FOR THE DRINKING
 FOUNTAIN FOR STANDING PERSON USE SHOWING SPOUT HEIGHT
 AND SPOUT LOCATION- SECTION 602.7 FBC ACC.
  
 6) P1 & P2: PROVIDE A WATER RISER DRAWING- SECTION
 107.3.5.1.3 WPB.
  
 7) P1 & P2: TWO NEW TENANT OCCUPANCIES ARE SHOWN. SHOW
 THE LOCATIONS OF THE NEW WATER METERS AND MAIN SHUTOFF
 VALVES TO THE SPACES- SECTIONS 605.1 & 606.1 FBC P.
  
 8) P1 & P2: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED AT THE LAVATORY PER SECTION 416.5. PLEASE NOTE
 THAT TEMPERED WATER SHALL BE SUPPLIED THROUGH A WATER
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070-
 SECTION 607.1.2 FBC P.
  
 9) P1 & P2: SHOW THE LOCATIONS OF WATER HAMMER
 ARRESTORS FOR SUPPLY LINES TO QUICK CLOSING VALVES-
 SECTION- 604.9 FBC P.
  
 10) P2: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER IN THE SCHEDULE- TABLE C404.2 FBC EC.
  
 11) P2, BAY 1B ISO: THE MOP SINK (P3) MUST BE
 INDIVIDUALLY VENTED BECAUSE IT CANNOT BE PART OF THE
 TOILET ROOM HORIZONTAL WET SYSTEM- SECTION 912.1 FBC P.
  
 12) P2, BAY 12 ISO: THE LAVATORY IS MISLABELED (P1)
 INSTEAD OF (P2).
  
 13) P2: SHOW THE TYPE AND SIZE OF HOT WATER PIPE
 INSULATION- TABLE C403.2.10 FBC EC.
  
 14) INDICATE THE TYPE OF WALL FINISHES TO BE INSTALLED
 IN THE RESTROOMS AND AT THE MOP SINK LOCATIONS IN
 ACCORDANCE WITH SECTION 310.3 FBC P, AND 1210.2.2 FBC
 B.
  
 15) PROVIDE A PLUMBING SUB-PERMIT APPLICATION- SECTION
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  