Plan Review Notes
Plan Review Notes For Permit 20100803
Permit Number 20100803
Review Stop B
Sequence Number 1
Notes
Date Text
2020-10-29 10:30:34WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20100803
 ADD: 7032 & 7036 OKEECHOBEE BLVD.
 CONT: ELE8 CONSTRUCTION, INC.
 TEL: 561-430-4870
 E-MAIL: BOB#MWARCHITECTURE.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. OCT. OCT. 29TH/2020
 ACTION: DENIED
  
 1A) PLEASE NOTE THIS PERMIT APPLICATION CAME IN FOR TO
 1ST TIME TENANT BUILDOUTS THAT BOTH SUITES 7032 & 7036
 WILL REQUIRE CERTIFICATES OF OCCUPANCY. PLEASE PROVIDE
 THE PERMIT LIBRARIAN WITH A 2ND PERMIT APPLICATION FOR
 THE 2ND TENANT SPACE. FESS WILL ALSO NEED TO BE
 ADJUSTED ACCORDINGLY FOR BOTH PERMITS.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 111.2
 CERTIFICATE OF OCCUPANCY.
 1B) SHEET A-0.1 LIST THE PROJECT SPECIFIC CODE SUMMARY,
 LISTING A PRIMARY OCCUPANCY MERCANTILE AND SECONDARY
 OCCUPANCY BUSINESS. BECAUSE OF THE REQUIRED CERTIFICATE
 OF OCCUPANCY REQUIREMENTS 2 PERMITS REQUIRED, PLEASE
 LIST THE OCCUPANCIES BY THEIR ADDRESS. EXAMPLE 7032-
 MERCANTILE/ RETAIL AND 7036- BUSINESS. WE CAN HAVE ONE
 SET OF PLANS TO SHARE FOR THE 2 PERMITS.
 2) WITHIN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY
 SHEET FOR EITHER OF THE TENANT SPACES NOR CHAPTER 10
 MEANS OF EGRESS.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA.2017 FLORIDA
 BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE
 SECTION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
  
 MISSING CODE DATA:
 LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE
 FOLLOWING:
 WALLS
 FURNITURE LAYOUT
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS OR NET
 DEAD END CORRIDORS
 DOOR SWING
 MEANS OF EGRESS EXIT ACCESS
 EXIT
 EXIT DISCHARGE / HOW MANY REQUIRED/ HOW MANY PROVIDED
  
 3) SHEET A-0.1 INDICATES UNDER THE HEADING OF DEFERRED
 SUBMITTALS DESIGN PRESSURES FOR ALUMINUM STOREFRONT AND
 A
 ALUMINUM DOORS, BUT THERE IS NO WIND DESIGN CRITERIA
 PROVIDED FOR THE PRESSURES.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 3.2. RISK CATEGORY.
  
 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1.
  
 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
  
 4) THERE ARE NO SHEETS WITHIN THE PLAN SET SHOWING
 WHERE THE STOREFRONT WINDOW AND DOORS ARE TO BE
 INSTALLED? 107.2.1.2. ADDITIONAL INFORMATION REQUIRED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND
 OR STRUCTURES.
 107.3.5.1 COMMERCIAL BUILDINGS
 107.3.5.1.1. BUILDING
 ELEVATIONS.
  
 5) SHEET A-520 ROOM FINISH SCHEDULE INDICATES THE WALLS
 TO BE GYPSUM/ PAINT. 2017 FBC-B 1210.2.2. WALLS &
 PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING
 OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO
 LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE.
 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4
 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT
 IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 6) SHEET A-5200 RESTROOM ELEVATIONS:
 6A) IN ELEVATIONS A & B THE GRAB BARS ARE DIMENSIONED
 TO THE CENTERLINE OF THE GRAB BAR, NOT THE TOP OF THE
 GRAB BAR, THE GRIPPING SURFACE. 2017 FBC-ACCESSIBILITY
 CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS
 SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT
 CENTERLINE.
  
 6B) ELEVATION A THERE IS NO DIMENSION FOR THE ELEVATION
 OF THE MIRROR OVER THE SINK. 603.3 MIRRORS. 2017
 FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE
 LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE
 BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
  
 6C) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 FBC-
 ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH:
 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS.
 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE
 BETWEEN 38TO 43 INCHES ABOVE FINISH FLOOR.
  
 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  