| 2020-10-29 10:30:34 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20100803 |
| | ADD: 7032 & 7036 OKEECHOBEE BLVD. |
| | CONT: ELE8 CONSTRUCTION, INC. |
| | TEL: 561-430-4870 |
| | E-MAIL: BOB#MWARCHITECTURE.COM |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: THURS. OCT. OCT. 29TH/2020 |
| | ACTION: DENIED |
| | |
| | 1A) PLEASE NOTE THIS PERMIT APPLICATION CAME IN FOR TO |
| | 1ST TIME TENANT BUILDOUTS THAT BOTH SUITES 7032 & 7036 |
| | WILL REQUIRE CERTIFICATES OF OCCUPANCY. PLEASE PROVIDE |
| | THE PERMIT LIBRARIAN WITH A 2ND PERMIT APPLICATION FOR |
| | THE 2ND TENANT SPACE. FESS WILL ALSO NEED TO BE |
| | ADJUSTED ACCORDINGLY FOR BOTH PERMITS. |
| | 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATIVE CODE SECTION 111.2 |
| | CERTIFICATE OF OCCUPANCY. |
| | 1B) SHEET A-0.1 LIST THE PROJECT SPECIFIC CODE SUMMARY, |
| | LISTING A PRIMARY OCCUPANCY MERCANTILE AND SECONDARY |
| | OCCUPANCY BUSINESS. BECAUSE OF THE REQUIRED CERTIFICATE |
| | OF OCCUPANCY REQUIREMENTS 2 PERMITS REQUIRED, PLEASE |
| | LIST THE OCCUPANCIES BY THEIR ADDRESS. EXAMPLE 7032- |
| | MERCANTILE/ RETAIL AND 7036- BUSINESS. WE CAN HAVE ONE |
| | SET OF PLANS TO SHARE FOR THE 2 PERMITS. |
| | 2) WITHIN THE SUBMITTED PLANS THERE IS NO LIFE SAFETY |
| | SHEET FOR EITHER OF THE TENANT SPACES NOR CHAPTER 10 |
| | MEANS OF EGRESS. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA.2017 FLORIDA |
| | BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | SECTION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | |
| | MISSING CODE DATA: |
| | LIFE SAFETY PLANS SHALL DETERMINE AND SHALL INCLUDE THE |
| | FOLLOWING: |
| | WALLS |
| | FURNITURE LAYOUT |
| | OCCUPANT LOAD AND EGRESS CAPACITIES |
| | GROSS OR NET |
| | DEAD END CORRIDORS |
| | DOOR SWING |
| | MEANS OF EGRESS EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE / HOW MANY REQUIRED/ HOW MANY PROVIDED |
| | |
| | 3) SHEET A-0.1 INDICATES UNDER THE HEADING OF DEFERRED |
| | SUBMITTALS DESIGN PRESSURES FOR ALUMINUM STOREFRONT AND |
| | A |
| | ALUMINUM DOORS, BUT THERE IS NO WIND DESIGN CRITERIA |
| | PROVIDED FOR THE PRESSURES. |
| | 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 3.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS |
| | DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1. |
| | |
| | 3.2. RISK CATEGORY. |
| | |
| | 3.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. ASCE 7-10 TABLE 30.3.1. |
| | |
| | 3.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 3.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED |
| | BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR |
| | THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | 3.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED |
| | CONVERSION VULT TO VASD. |
| | |
| | |
| | 4) THERE ARE NO SHEETS WITHIN THE PLAN SET SHOWING |
| | WHERE THE STOREFRONT WINDOW AND DOORS ARE TO BE |
| | INSTALLED? 107.2.1.2. ADDITIONAL INFORMATION REQUIRED. |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS AND |
| | OR STRUCTURES. |
| | 107.3.5.1 COMMERCIAL BUILDINGS |
| | 107.3.5.1.1. BUILDING |
| | ELEVATIONS. |
| | |
| | 5) SHEET A-520 ROOM FINISH SCHEDULE INDICATES THE WALLS |
| | TO BE GYPSUM/ PAINT. 2017 FBC-B 1210.2.2. WALLS & |
| | PARTITIONS. THIS COMMENT IS A RESULT OF THE BUILDING |
| | OFFICIAL INTERPRETATION. IN RESTROOMS EPOXY PAINT IS NO |
| | LONGER CONSIDERED A SMOOTH HARD, NON-ABSORBENT SURFACE. |
| | WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE SINKS, |
| | URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH, HARD, |
| | NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS THAN 4 |
| | FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL ELEMENTS, |
| | THE MATERIAL USED IN SUCH WALLS SHALL BE OF A TYPE THAT |
| | IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | |
| | 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS |
| | SHALL COMPLY WITH 1210.2. |
| | |
| | 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND |
| | PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH |
| | SECTIONS 1210.1 THROUGH 1210.4. |
| | |
| | 6) SHEET A-5200 RESTROOM ELEVATIONS: |
| | 6A) IN ELEVATIONS A & B THE GRAB BARS ARE DIMENSIONED |
| | TO THE CENTERLINE OF THE GRAB BAR, NOT THE TOP OF THE |
| | GRAB BAR, THE GRIPPING SURFACE. 2017 FBC-ACCESSIBILITY |
| | CODE SECTION 609.4 POSITION OF GRAB BARS. GRAB BARS |
| | SHALL BE INSTALLED IN A HORIZONTAL POSITION, 33 INCHES |
| | MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR |
| | MEASURED TO THE TOP OF THE GRIPPING SURFACE, NOT |
| | CENTERLINE. |
| | |
| | 6B) ELEVATION A THERE IS NO DIMENSION FOR THE ELEVATION |
| | OF THE MIRROR OVER THE SINK. 603.3 MIRRORS. 2017 |
| | FBC-ACCESSIBILITY CODE. MIRRORS LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. |
| | |
| | 6C) SPOUT OUTLETS/ DRINKING FOUNTAINS. 2017 FBC- |
| | ACCESS. CODE. SPOUT OUTLETS SHALL COMPLY WITH: |
| | 602.4 SPOUT HEIGHT. 36 INCHES MAXIMUM ABOVE THE FINISH |
| | FLOOR OR GROUND FOR WHEELCHAIR BOUND INDIVIDUALS. |
| | 602.7 SPOUT HEIGHT FOR THE STANDING PERSONS SHALL BE |
| | BETWEEN 38TO 43 INCHES ABOVE FINISH FLOOR. |
| | |
| | 7) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| | 19 |
| | IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| | 561-718-9724. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |