| 2020-11-09 20:27:25 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SERVICE CONDUCTORS ARE SHOWN WITH AN EGC. EGC |
| | ORIGINATES AFTER SERVICE DISCONNECTING MEAN'S OCP. |
| | PLEASE REMOVE EGC FROM SERVICE ENTRANCE CONDUCTORS. NEC |
| | 250.24B |
| | |
| | 2. XFMR FEEDING PANEL T MUST HAVE NO LESS THAN 125% OF |
| | THE SECONDARY CURRENT OF THE XFMR AT PANEL T FOR OCP. |
| | 286A X 1.25= 357.5A. NEXT STANDARD SIZE OCP IS 400AMPS. |
| | NEC 408.36 450.3(B) 215.3(A) |
| | |
| | 3.VALUE LOW FOR AMOUNT OF WORK SHOWN. PROVIDE SIGNED |
| | CONTRACT BY BOTH OWNER AND CONTRACTOR WITH AN ACCURATE |
| | VALUE. IF AN ACCURATE VALUE CANNOT BE ESTABLISHED VALUE |
| | MAY BE SET BY BUILDING OFFICAL. FBC 109.3 |
| | |
| | 4. A FIRE PUMP IS SHOWN ON THE RISER DIAGRAM. WILL PART |
| | OF THIS SERVICE REMAIN AND BE THE PERMANENT SERVICE FOR |
| | THE BUILDING? FBC 107.2.1 |
| | |
| | 5. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| | UILDING-PERMIT-FORMS |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |