| 2020-10-27 16:07:20 | 10/27/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE PROVIDE MORE INFORMATION AS THERE ARE TWO |
| | DIFFERENT PERMITS AND AN OR APPLICATION FOR A PERMIT ON |
| | THIS ADDRESS. THE OWNER AND THE CONTRACTOR HAVE TO WORK |
| | TOGETHER FOR CODE COMPLIANCE, WE WOULD LIKE TO HAVE |
| | THIS IN WRITING WITH A LETTER OF UNDERSTANDING SIGNED |
| | BY ALL PARTIES, AS TO WHO IS RESPONSIBLE AND WHAT SCOPE |
| | OF WORK OF WHAT TAKING PLACE TO DEFINE THE |
| | RESPONSIBILITIES PE THE 2017 FBC WPB A 101.2 SCOPE. |
| | |
| | 2. THE PLANS SUBMITTED SAY REVISION BUT ON A PERMIT, IT |
| | COMES IN AS A COMMERICAL MICS PLEASE CLARIFY WHAT IS ON |
| | THE SCOPE AND WHY A COMMERCIAL MISC IS ON PERMIT |
| | DOCUMENTS PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |