Plan Review Notes
Plan Review Notes For Permit 20100756
Permit Number 20100756
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-10-22 15:03:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE INDICATIONS OF ANTENNA LOCATIONS; HOWEVER,
 THERE IS NO SPECTRUM RADIO SIGNAL STRENGTH SURVEY THAT
 WOULD INDICATE WHERE TO PUT THE DEVICES.
  
 PLEASE PROVIDE THIS SURVEY AS IT WILL ALSO BE USED TO
 COMPARE IT AFTER THE BDA IS INSTALLED AND TURNED ON BY
 AFTER REVIEW BY PBC RADIO MANAGER AND THE NEW SURVEY IS
 PRODUCED.
  
 THE NEW SURVEY SHALL BE SUBMITTED AS A SUBMITTAL TO
 THIS PERMIT AND SHALL BE REVIEWED AND APPROVED PRIOR TO
 FINAL PORTABLE RADIO TESTING AND APPROVAL.
  
  
  
 2) YOU SHALL MAKE CONTACT AND COORDINATE WITH MARK
 FILLA, PALM BEACH COUNTY, PUBLIC SAFETY RADIO SYSTEMS
 MANAGER, FOR ALL RADIO SIGNAL DETAILS, OUTBOUND SIGNAL
 STRENGTH AND ANTENNA DIRECTION, AS OUR RADIOS OPERATE
 ON THAT SYSTEM.
  
 [email protected] 561-233-0837
  
 YOU SHALL NOT TURN THE SYSTEM ON PRIOR TO REVIEW AND
 APPROVAL BY MR. FILLA.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  