Plan Review Notes
Plan Review Notes For Permit 20100750
Permit Number 20100750
Review Stop P
Sequence Number 1
Notes
Date Text
2020-10-28 16:30:3310/28/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON THE COVER SHEET IN THE DRAWING INDEX YOU HAVE
 UNDER ELECTRICAL P100 AND NO P100 WAS SUBMITTED. IN THE
 SAME INDEX YOU HAVE UNDER MECHANICAL M100 WHICH HAS
 ENLARGED APARTMENT M & P, CAN YOU PLEASE TRY TO
 SEPARATE THEM BY PUTTING P100 IN WITH PLUMING ON ITS
 OWN IS POSSIBLE PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. THIS BUILDING WAS CONSTRUCTED UNDER THE FEDERAL FAIR
 HOUSING ACCESSIBILITY GUIDELINES. PLEASE INDICATE ON
 PLANS WHICH DESIGN SPECIFICATION ( "A" OR "B" OF THE
 ACT) WAS USED IN THE ORIGINAL DESIGN OF THESE UNITS.
 TELL US WHICH USABLE BATHROOM IN THE DWELLING UNITS,
 THE ALTERATION THAT IS PROPOSED IN THE BATHROOM SHALL
 ALSO BE IN COMPLIANCE WITH THE FEDERAL FAIR HOUSING
 ACCESSIBILITY GUIDELINES PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PLEASE PROVIDE A G103 PAGE THAT SHOWS THE GOVERNING
 CODE FOR THE FEDERAL FAIR HOUSING ACCESSIBILITY
 GUIDELINES THAT YOU ARE USING PER WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. PER THE ORIGINAL RESPONSE FROM E & A ARCHITECTS
 DATED 6/16/20 UNIT RENOVATIONS WERE TO BE UNDER A
 SEPARATE PERMIT. ARE THOSE ACCESSIBLE UNITS DONE UNDER
 THIS PERMIT REVISION? IF SO PLEASE CLARIFY THE FHA
 GUIDELINES FOR THE ACCESSIBLE UNITS ON OF THIS REVISION
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. THE SCOPE OF WORK ON THE PLANS STATES THE TOILETS
 WILL BE REPLACED BUT THE TOILETS AND LAVATORIES ARE
 BEING FLIPPED IN THEIR LOCATIONS IN THE ACCESSIBLE
 UNITS, THE KITCHEN SINKS ARE BEING RELOCATED IN THE TWO
 AND THREE-BED ACCESSIBLE UNITS, AND THE WASHER IS BEING
 RELOCATED IN THE TWO-BED ACCESSIBLE UNIT. THESE CHANGES
 NEED TO BE NOTED IN PLUMBING NOTES ON THE PLANS PER THE
 WPB AMEND. TO FBC SEC. 107.2.1.
  
 6. ON SHEET 203, 204, AND 205 YOU HAVE ON DRAWING
 DETAIL #2 FBC ACCESSIBLE LABELED AS THIS IS FHA
 GUIDELINES PLEASE CORRECT OR CLARIFY BY NOTING WHICH
 YOU ARE BEING USED PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. PLEASE PROVIDE A WATER RISER DIAGRAMS FOR THE
 RELOCATED FIXTURES PER THE WPB AMEND TO FBC
 SEC.107.3.5.1.3.
  
 8. ON SHEET M101 FOR LB1 IN THE STANDPIPE SERVING OF
 THE AUTOMATIC CLOTHES WASHER SHALL CONNECT TO A 3-INCH
 PER THE 2017 FBC SEC. 406.2 WASTE CONNECTION.
  
 9. ON SHEETS A203, 204 & A 205 - SHOW THE DIMENSION OF
 THE MINIMUM CLEAR FLOOR SPACE ALL FIXTURE ON THE PLANS
 PER THE FHA GUIDELINES.
  
 10. ON SHEET A204 AND 205 THE TUB ARE SHOWN AS
 ACCESSIBLE BUT NO DETAILS ON G102 WHICH WERE SHOWN ON
 THE PRIOR VERSION OF PLANS, PLEASE SHOW THE LOCATION OF
 THE GRAB BARS, THE CONTROL AREA, AND BATHTUB WITH BENCH
 DETAIL WITH THE GRAB BAR 24 INCHES LONG MINIMUM SHALL
 BE INSTALLED ON THE CONTROL END WALL AT THE FRONT EDGE
 OF THE BATHTUB THAT COMPLIES WITH THE FHA ACCESSIBILITY
 GUIDELINES.
  
 11. THE CABINET FOR THE LAVATORY NEXT TO THE SHOWER
 SHALL BE A REMOVABLE CABINET PER THE FHA ACCESSIBILITY
 GUIDELINES REQ. #7, PLEASE NOTE ON A203, 204, AND 205
 PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 12. ON G102 PLEASE SHOW THE REINFORCEMENT FOR THE
 SHOWER SEAT IN DETAIL OF 24 INCHES PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 13. ON G102 THE DETAIL FOR THE WATER CLOSE OF THE FHA
 GUIDELINE IS 1' 6" FOR TYPE A AND B UNITS. PLEASE
 CHANGE AND ADD TO THE APPROACH AND STANDARD DETAIL, SEE
 FIG 6 OF THE FHAG PER THE WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  