| Plan Review Notes For Permit 20100738 |
| Permit Number |
20100738 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-06-16 10:36:57 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | BUILDING REVIEW DENIED: | | | | | | 3RD BUILDING REVIEW DENIED: | | | | | | THE FOLLOWING ITEMS FROM LAST REVIEW ARE STILL PENDING: | | | | | | 4) FAILED, PROVIDE A CLARIFICATION AS THE FOUNDATION | | | PLANS INDICATE FOOTINGS AT A DEPTH OF 16" BELOW GRADE | | | AND THE GEOTECH REPORT STATES THAT THE FOOTINGS SHOULD | | | BOTTOM AT 18" BELOW GRADE. | | | | | | 8) & 9) THE SUBMITTED PRODUCT APPROVALS NEED TO BE | | | REVIEW STAMPED BY DESIGNER OF RECORD. IF THESE PRODUCT | | | APPROVALS ARE TO BE DEFERRED, PLEASE PROVIDE A LIST ON | | | SUBMITTALS THAT ARE TO BE DEFERRED. |
|