| Plan Review Notes For Permit 20100738 |
| Permit Number |
20100738 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-02-04 06:21:49 | THE CFM'S OF THE NEW EXHAUST FAN IS 194 CFM. PLEASE | | | PROVIDE CALCULATIONS FOR THE EXHAUST FOR EACH DIFFERENT | | | SIZE OF GARAGE. THE 194 CFM IS NOT ENOUGH BASED ON | | | TABLE 403.3.1.1 FBC M 403.3.1.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|