Plan Review Notes
Plan Review Notes For Permit 20100738
Permit Number 20100738
Review Stop E
Sequence Number 2
Notes
Date Text
2021-02-08 11:00:44CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 PREVIOUS COMMENTS:
  
 1) PLEASE SUBMIT SHORT CIRCUIT CALCULATIONS AND
 AVAILABLE FAULT CURRENTS FOR PANEL G2. FCB 107
  
 CALCULATIONS REQUESTED WERE FOR AVAILABLE SHORT CIRCUIT
 CURRENTS NOT FOR LOAD CALCULATIONS. PLEASE SUBMIT
 AVAILABLE SHORT CIRCUIT CURRENT AND SHORT CIRCUIT
 CALCULATIONS AS REQUESTED.
  
 ADDITIONAL COMMENTS:
  
 2) NEW SHEET GA2 -0.0 INDEX OF DRAWINGS: NEWLY REVISED
 SHEET LISTS THREE ELECTRICAL DRAWINGS (E-1.0, E-1-1,
 AND E-GII.1). ONLY THE E-GII.1 ELECTRICAL SHEET HAS
 BEEN SUBMITTED. PLEASE CLARIFY AND UPLOAD MISSING
 DRAWINGS IF NEEDED.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  