Plan Review Notes
Plan Review Notes For Permit 20100738
Permit Number 20100738
Review Stop B
Sequence Number 2
Notes
Date Text
2021-02-16 12:10:18 
 PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 GARAGE ( TYPE II ) / DETACHED PRIVATE GARAGE BUILDING
 (7 UNITS PLUS 1 STORAGE)
 TYPE V-B CONSTRUCTION, UNSPRINKLERED
 GROUP U OCCUPANCY
  
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT RESOLVED. I DO NOT SEE THAT THE PROPOSED SLAB
 ELEVATIONS IN NAVD 88 VERTICAL DATUM IS SPECIFIED ON
 THE ARCHITECTURAL PLANS AS REQUESTED. FBC
 AMEND.107.2.1.2 THE PROPOSED FLOOD VENTS IN THE GARAGE
 DOORS DO NOT COMPLY WITH FEMA TECHNICAL BULLETIN 1 FOR
 WET FLOOD PROOFING. AT LEAST 2 FLOOD OPENINGS ARE
 REQUIRED ON DIFFERENT SIDES OF THE ENCLOSURE. THE
 REQUIRED NET OPEN AREA FOR NON-ENGINEERED FLOOD VENTS
 IS 1 SQUARE INCH FOR EACH SQUARE FOOT OF ENCLOSED AREA
 (MEASURED ON THE EXTERIOR OF THE ENCLOSURES WALLS).
 ONLY THE NET FREE AREA EXCLUDING LOUVERS, SCREENS, ETC.
 CAN BE COUNTED. THE SPACES BETWEEN GARAGE DOORS AND
 JAMBS OR WALLS CAN NOT BE COUNTED. ONLY THE NET AREA OF
 THE VENTS THAT AREA BELOW DFE CAN BE COUNTED. VENTS IN
 FIRE RATED WALLS ARE REQUIRED TO HAVE A FIRE RATING AS
 REQUIRED FOR THE WALL. SEE FEMA TB 1 FOR GUIDANCE. YOU
 ALSO HAVE THE OPTION TO ELEVATE THE GARAGES TO THE DFE
 OR TO DRY FLOOD PROOF THE DETACHED GARAGES.
 THIS PROJECT IS IN A SPECIAL FLOOD HAZARD AREA, AE. THE
 BFE IS 14' NAVD88 AND THE DFE IS 16' NAVD88. THE FINISH
 FLOOR ELEVATION OF THE GARAGE IS SPECIFIED AS 15'
 NAVD88. THIS IS ONE FOOT BELOW THE REQUIRED DFE AND
 WILL BE REQUIRED TO BE DESIGNED WITH FLOOD VENTS OR BE
 FLOOD PROOFED. PROVIDE A DESIGN THAT COMPLIES WITH THE
 CITY'S FLOOD ORDINANCE. SPECIFY THE PROPOSED ELEVATION
 OF THE GARAGE SLAB, IN NAVD 88 VERTICAL DATUM, ON THE
 ARCHITECTURAL PLANS. FBC 1612
  
 2) RESOLVED. PROVIDE A DETAIL FOR THE REQUIRED ONE HOUR
 FIRE RESISTIVE RATED CEILING ASSEMBLY AND THE LISTING
 INFORMATION. FBC 711
  
 3) RESOLVED. PROVIDE A DETAIL FOR THE LISTED JOINT
 TREATMENT THAT WILL BE USED AT THE INTERSECTION OF THE
 ONE HOUR FIRE RESISTIVE RATED THE INTERIOR WALLS AND
 CEILINGS. FBC 715
  
 4) PARTIALLY RESOLVED. THE DATE ON THE REVISED
 GEOTECHNICAL REPORT IS 1/1/2020 AND THE YEAR SHOULD BE
 2021. SECTION 4.2 ON THE GEOTECHNICAL REPORT STATES
 THAT THE FOOTINGS SHOULD BOTTOM AT LEAST 18" BELOW
 FINAL GRADE. SHOW HOW THIS BUILDING WILL MEET THIS
 REQUIREMENT. FBC 107.2
  
 5) NOT RESOLVED. WALL SECTION 2 ON SHEET GA-2, SHOWS
 THE BOTTOM OF THE FOOTER 8" BELOW GRADE. FBC REQUIRES
 THE BOTTOM OF FOOTINGS TO BE A MINIMUM OF 12" BELOW
 GRADE. FBC 1809.5
  
 6) RESOLVED. ON SHEET GA-2 THE FIRE RATED WALLS, TYPE
 L, BETWEEN THE GARAGE STALLS ARE SPECIFIED AS 8"
 MASONRY. DETAIL D ON S-GA.2.2 IS FOR A 4" X 4" CONCRETE
 CAP AT THESE LOCATIONS WITH ONLY THE CONCRETE SLAB AND
 NO FOOTING. PLEASE COORDINATE. FBC 107.2
  
 7) RESOLVED. PROVIDE STRUCTURAL DETAILS FOR THE TYPE L
 FIRE RATED MASONRY WALLS BETWEEN THE GARAGES. SPECIFY
 THE FOOTING, WALL AND TIE BEAM REINFORCING. FBC 2101
  
 8) PARTIALLY RESOLVED.
 A) ROOF TILE: THE PRODUCT APPROVAL FOR THE ROOF TILE
 DOES NOT HAVE THE COVER SHEET WITH THE FLORIDA PRODUCT
 APPROVAL NUMBER THAT REFERENCES THE EVALUATION REPORT
 THAT WAS SUBMITTED. HIGHLIGHT OR CIRCLE THE SPECIFIC
 TYPE AND NUMBER OF FASTENERS THAT WILL BE USED TO
 ATTACH THE ROOF TILES. IF AN ADHESIVE WILL BE USED,
 SUBMIT THE PRODUCT APPROVAL FOR IT.
 B) GARAGE DOOR: THE PRODUCT APPROVAL DRAWINGS FOR THE
 OVERHEAD GARAGE DOORS ARE INCOMPLETE. A PORTION OF THE
 UPLOADED DRAWINGS ARE MISSING. PLEASE SUBMIT COMPLETE
 DRAWINGS.
 C) NO PRODUCT APPROVALS WERE SUBMITTED FOR THE OUTSWING
 SIDE HINGED DOORS.
 D) SUBMIT THE PRODUCT APPROVALS WITH A SHOP REVIEW
 STAMP MARKED APPROVED BY THE DESIGNER OF RECORD FOR THE
 PROJECT.
 FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE DIFFERENT ROOFING
 MATERIALS, ROOF VENTS, SWING DOORS AND OVERHEAD GARAGE
 DOORS. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 9) DEFERRED. SUBMIT TRUSS DRAWINGS AND A TRUSS LAYOUT
 PLAN. FBC 2303.4 THESE ITEMS CAN BE DEFERRED IF
 REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 10) NOTE: FBC 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 11) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
 12) THE OUTSWING SIDE HINGED DOOR IS NOT SPECIFIED IN
 THE DOOR SCHEDULE ON GA-2.
  
  
  


Account Summary | Usage Policy | Privacy Policy