Plan Review Notes
Plan Review Notes For Permit 20100738
Permit Number 20100738
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-30 09:24:32CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PANEL G2 IS MLO AND RISER DOES NOT SHOW A SERVICE
 DISCONNECT. A SERVICE RATED MAIN DISCONNECT AND MCB ARE
 REQUIRED. NEC 230.70, NEC 230.90
 2) PLEASE SUBMIT SHORT CIRCUIT CALCULATIONS AND
 AVAILABLE FAULT CURRENTS FOR PANEL G2. FCB 107
 3) PANEL SCHEDULE G2 HAS A NOTE SHOWING A PANEL PV
 CALCULATION. THIS PANEL IS NOT SHOWN ANYWHERE ELSE AND
 IS NOT PART OF THE RISER DIAGRAM. THIS LOAD IS NOT
 INCLUDED IN ANY OF THE LOAD CALCULATIONS EITHER. PLEASE
 CLARIFY. FCB 107
 4) PLEASE SEE COMMENTS FROM BUILDING REVIEWER REGARDING
 STRUCTURE BEING ON A SPECIAL FLOOD ZONE AND
 REQUIREMENTS FOR EQUIPMENT LOCATION. FINAL APPROVAL IS
 SUBJECT TO COMPLIANCE WITH THESE REQUIREMENTS.
  
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  