| 2021-02-26 17:36:13 | 02/26/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON COMMENTS ONE THOUGH 5, I MAY NOT HAVE PUT IN THE |
| | INCORRECT COMMENT SO THE RESPONSE IS FOR THE CLUBHOUSE. |
| | IF YOU REFER TO THE COMMENTS ON THE MASTER AS I DID A |
| | COPY AND PASTE AND MAY HAVE DONE IT WRONG AND I |
| | APOLOGIZE FOR IT. |
| | |
| | 6. YOU CAN KEEP THE PERFORATED CAPS, BUT THE ISSUE IS |
| | NOT THE VENT. IT IS THE POSITIVE AND NEGATIVE FLOW. IF |
| | YOU PUT AN A.A.V IN A PLENUM, IT NEEDS AN ACCESS PANEL, |
| | AND THE PVC IS NOT A FIRE-RATED ASSEMBLE IN THE SMOKE |
| | INDEX WON?T WORK. A SUGGESTION IS TO TIE THE HEATER PAN |
| | AND CONDENSATE TOGETHER AND CONVERT TO CPVC THEN OFFSET |
| | INTO THE PLENUM. IN OTHER PLANS FOR THE REVIEWS, THEY |
| | ARE THE SAME COMMENT, SO PLEASE CALL ME FOR |
| | CLARIFICATION. |
| | |
| | 7. DONE. |
| | |
| | 8. COULD NOT FIND THE PAGES ARE CROSSED WITH 6.2.1. |
| | CALL ME ON THIS ONE, TOO, PLEASE. |
| | |
| | 9. SHEET P5.2.4; |
| | A. DONE. |
| | |
| | B. PIPE IS STILL MISSING SIZES. |
| | |
| | C. PAGE 6.1.1 NOT FOUND. |
| | |
| | D. THE FLOOR DRAIN IS NOT VENTED PER THE 2017 FBC SEC. |
| | 901.2.1 VENTING REQUIRED. |
| | |
| | E. PIPE FOR ELEVATOR DRAIN STILL NOT LABEL ON SIZE. |
| | |
| | 10. DONE. |
| | |
| | 11. THERMAL EXPANSION COULD NOT BE FOUND AS 6.2.2 IS |
| | THE SAME AS 6.1.1. THE COMMENT IS TO THE WATER HEATER |
| | THAT SHOWS A METER. IF THAT METER DOES NOT FLOW EITHER |
| | WAY, THEN AN EXPANSION VALVE WILL BE NEEDED AT THE SIDE |
| | OF THE OUTLET METER. IF YOU LIKE YOU CAN CALL ME TO |
| | DISCUSS THIS. |
| | |
| | 12. DONE |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |