Plan Review Notes
Plan Review Notes For Permit 20100736
Permit Number 20100736
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-26 17:36:1302/26/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON COMMENTS ONE THOUGH 5, I MAY NOT HAVE PUT IN THE
 INCORRECT COMMENT SO THE RESPONSE IS FOR THE CLUBHOUSE.
 IF YOU REFER TO THE COMMENTS ON THE MASTER AS I DID A
 COPY AND PASTE AND MAY HAVE DONE IT WRONG AND I
 APOLOGIZE FOR IT.
  
 6. YOU CAN KEEP THE PERFORATED CAPS, BUT THE ISSUE IS
 NOT THE VENT. IT IS THE POSITIVE AND NEGATIVE FLOW. IF
 YOU PUT AN A.A.V IN A PLENUM, IT NEEDS AN ACCESS PANEL,
 AND THE PVC IS NOT A FIRE-RATED ASSEMBLE IN THE SMOKE
 INDEX WON?T WORK. A SUGGESTION IS TO TIE THE HEATER PAN
 AND CONDENSATE TOGETHER AND CONVERT TO CPVC THEN OFFSET
 INTO THE PLENUM. IN OTHER PLANS FOR THE REVIEWS, THEY
 ARE THE SAME COMMENT, SO PLEASE CALL ME FOR
 CLARIFICATION.
  
 7. DONE.
  
 8. COULD NOT FIND THE PAGES ARE CROSSED WITH 6.2.1.
 CALL ME ON THIS ONE, TOO, PLEASE.
  
 9. SHEET P5.2.4;
 A. DONE.
  
 B. PIPE IS STILL MISSING SIZES.
  
 C. PAGE 6.1.1 NOT FOUND.
  
 D. THE FLOOR DRAIN IS NOT VENTED PER THE 2017 FBC SEC.
 901.2.1 VENTING REQUIRED.
  
 E. PIPE FOR ELEVATOR DRAIN STILL NOT LABEL ON SIZE.
  
 10. DONE.
  
 11. THERMAL EXPANSION COULD NOT BE FOUND AS 6.2.2 IS
 THE SAME AS 6.1.1. THE COMMENT IS TO THE WATER HEATER
 THAT SHOWS A METER. IF THAT METER DOES NOT FLOW EITHER
 WAY, THEN AN EXPANSION VALVE WILL BE NEEDED AT THE SIDE
 OF THE OUTLET METER. IF YOU LIKE YOU CAN CALL ME TO
 DISCUSS THIS.
  
 12. DONE
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  