| 2021-02-04 07:50:20 | 1ST REVIEW FBC-2020 MECHANICAL |
| | PERMIT-20100736 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2020 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2020 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M-4.2.1: PLEASE PROVIDE THE CALCULATIONS FOR |
| | EACH DRYER DUCT LENGTH AND EXPLAIN WHY A LONG VENT |
| | DRYER IS NOT REQUIRED. THE DRYER DUCT LENGTH LISTED IN |
| | EACH CHART, IS THAT LENGTH BEFORE THE 90 DEGREE AND 45 |
| | DEGREE TURNS? PROVIDE THE DEVELOPED LENGTH OF PIPE |
| | BEFORE THE TURNS ARE ADDED. FROM OUR CONVERSATION YOU |
| | MUST SUBTRACT 10? FROM THE DRYER MANUFACTURERS DRYER |
| | DUCT LENGTH. EXAMPLE: A1 THE LENGTH IS 54? ? 10? = 44?; |
| | THE DRYER EXHAUST LENGTH LISTS 40? WITH THE ADDITION OF |
| | 1 90 DEGREE AND 1 45 DEGREE TURN THIS BRINGS THE TOTAL |
| | ALLOWABLE LENGTH OF DRYER DUCT PIPING TO 36.5? WHICH IS |
| | LONGER THAN ALLOWED BY THE FBC M 504.8.4 WHICH WOULD |
| | MEAN THE LENGTH IDENTIFICATION MUST BE POSTED. FBC M |
| | 504.8.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |