| Plan Review Notes For Permit 20100736 |
| Permit Number |
20100736 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-02-18 09:36:16 | NEW 4 STORY APARTMENT BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 | | | AMENDMENTS | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | 1) I DID NOT CATCH THIS ON THE FIRST REVIEW - ALL UNIT | | | DOORS - PLEASE SHOW THE REQUIRED MANEUVERING SPACE (18" | | | BESIDE THE DOOR) TO EXIT THE UNIT OR ROOM. FBC | | | ACCESSIBILITY FHA REQUIREMENT ANSI 4.13.6 | | | 2) I DID NOT CATCH THIS ON THE FIRST REVIEW - UNIT A1 | | | DISTANCE FROM THE KITCHEN ISLAND TO THE WALL LEADING TO | | | THE KITCHEN (NO TURNING SPACE IN THE KITCHEN TO TURN | | | AROUND) NEEDS TO BE MIN. 40" (DRAWING A-4.2.1) - USABLE | | | KITCHENS WOULD MEET SECTION 100.205(C)(3)(IV) | | | IF:(B)CLEARANCE BETWEEN COUNTERS AND ALL OPPOSING BASE | | | CABINETS, COUNTERTOPS, APPLIANCES OR WALLS IS AT LEAST | | | 40 INCHES. | | | 3) WE ARE REQUIRING THAT YOU SHOW THE CLEAR FLOOR SPACE | | | FOR THE PLUMBING FIXTURES ON EACH UNIT FLOOR PLAN TO | | | SHOW THAT EACH UNIT COMPLIES WITH FAIR HOUSING | | | ACCESSIBILITY REQUIREMENTS. | | | 4) DRAWING (S-2.1.6) HAS A STRAP CONNECTOR SCHEDULE - | | | THE TRUSS FRAMING PLAN NEEDS TO SHOW THE LOCATION OF | | | THE TRUSS CONNECTORS (STRAPPING). | | | | | | | | | | | | | | | | | | |
|