Plan Review Notes
Plan Review Notes For Permit 20100736
Permit Number 20100736
Review Stop P
Sequence Number 1
Notes
Date Text
2020-12-01 13:12:3512/01/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. ON SHEET C-172 THERE ARE BACKFLOW SHOWN WITH DETAILS
 AND COMMENTS PLEASE ADD THAT SEPARATE PERMITS ARE
 REQUIRED BY A LICENSED CONTRACTOR AND CERTIFIED BY THE
 CITY OF WEST PALM BEACH UTILITIES DEPARTMENT PER THE
 WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 2. ON SHEET A10.2.1 AND A 10.2.2 PLEASE SHOW ALL CLEAR
 FLOOR SPACE DIMENSIONS FOR ALL AREAS PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION.
  
 3. ON SHEET A10.2.3 PLEASE REMOVE SHOWERS CLEAR FLOOR
 SPACE NOT USED IN THIS BUILDING AND ANY OTHER DETAILS
 THAT DO NOT APPLY TO THIS BUILDING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION.
  
 4. ON SHEET A10.2.1 FOR UNIT A1 WITH THE TUB OPTION, IT
 SHALL HAVE THE CLEAR FLOOR SPACE TO THE SIDE OF THE
 VALVE ACCESS IN ACCORDANCE WITH THE PARALLEL APPROACH
 FHADM 7.53.
  
 5. ON SHEET A10.2.1 AND 10.2.2 PLEASE PROVIDE DETAIL
 FOR LAV HEIGHT IN A10.2.3 THAT MEET THE REQUIREMENTS OF
 THE B BATHROOMS IN ACCORDANCE WITH THE FHADM 7.52.
  
 6. ON SHEET P5.2.1 FOR CONDENSATE AND PAN, IT HAS A
 PERFORATED CAP ON THE FOURTH FLOOR AND NOT VENT OR OUT
 THE WALL CAVITY PLEASE DETAIL OF A VENT THAT PROVIDES A
 FLOW OF AIR TO OR FROM A DRAINAGE SYSTEM, OR TO PROVIDE
 A CIRCULATION OF AIR WITHIN SUCH SYSTEM TO PROTECT TRAP
 SEALS FROM SIPHONAGE AND BACKPRESSURE PER THE 2017 FBC
 DEFINITIONS.
  
 7. ON SHEET P5.2.2 RISER 5 YOU HAVE A WASHING MACHINE
 ON A BATHROOM GROUP NOT ALLOWED PLEASE HAVE A SEPARATE
 STACK PER THE 2017 FBC SEC 912.2.1 HORIZONTAL WET VENT.
  
 8. ON SHEET P5.2.3 PLEASE VALVE AT ACCESSIBLE LOCATIONS
 FOR WATER RISERS PER THE 2017 FBC SEC. 606.1 LOCATION
 OF FULL-OPEN VALVES.
  
 9. SHEET P5.2.4;
 A. THERE ARE 5 WASHING MACHINES ON THE BATHROOM GROUP
 (NEXT TO STACK 5) THAT IS NOT ALLOWED PLEASE HAVE A
 SEPARATE STACK PER THE 2017 FBC SEC 912.2.1 HORIZONTAL
 WET VENT.
  
 B. PLEASE LABEL ALL PIPE SIZES FOR SANITARY DRAINAGE
 BRANCHES PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 C. PLEASE SHOW TRAP PRIMER FOR FLOOR DRAIN AND GIVE
 PAGE REFERENCE FOR DETAIL PER THE WPB AMENDMENTS TO THE
 FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 D. THE FLOOR DRAIN IS NOT VENTED PER THE 2017 FBC SEC.
 901.2.1 VENTING REQUIRED.
  
 E. PLEASE PROVIDE PIPE SIZE FOR THE SUMP PUMP DRAINAGE
 PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13)
 COMMERCIAL PLUMBING.
  
 10. SHEET P5.2.5 PLEASE PROVIDE PIPE SIZING FOR THE
 WATER RISER REQUIRED PER THE WPB AMENDMENTS TO THE FBC
 SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING.
  
 11. SHEET P6.2.1 THERE IS THE DETAIL FOR THE HEATER
 PLEASE PROVIDE THE THERMAL EXPANSION DEVICE PER THE
 2017 FBC SEC. FBC P 607.3.
  
 12. ON SHEET P6.2.2 UNDER ELECTRIC WATER SOURCE
 SCHEDULE HAS A MIN EFF. OF 0.92 BUT ACCORDING TO NEACA
 HOT WATER REGULATION 2015 AND IT SHOULD BE AT EF 0.95,
 PLEASE NOTE THAT 6.2.1 AND 6.2.2 ARE UPLOADED WITH THE
 NUMBER CROSSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved