| Plan Review Notes For Permit 20100735 |
| Permit Number |
20100735 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2021-06-22 17:35:54 | PLAN | | | REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | GARAGE ( TYPE 1 ) / DETACHED PRIVATE GARAGE BUILDING (8 | | | UNITS) | | | TYPE V-B CONSTRUCTION, UNSPRINKLERED | | | GROUP U OCCUPANCY | | | | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED (GARAGE | | | DOOR, ROOF TILE AND SMART VENTS) HAVE NOT BEEN APPROVED | | | IN WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4 | | | | | | 2) SUBMIT A PRODUCT APPROVAL FOR THE ROOF TILE | | | ADHESIVE. THE DESIGNER OF RECORD IS REQUIRED TO REVIEW | | | AND APPROVE IT IN WRITING. FBC 107.3.4 | | | | | | 3) SEPARATE PERMITS ARE REQUIRED FOR EACH OF THE | | | DETACHED GARAGE BUILDINGS. FBC 107.2.1 | | | | | | | | | | | | | | | |
|