| Plan Review Notes For Permit 20100735 |
| Permit Number |
20100735 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-11-05 11:50:34 | CODES IN EFFECT | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | | 6TH ED, CHAPTER 1. | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | | 6TH EDITION | | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | | 6TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | | | ELECTRICAL REVIEW STATUS: FAILED, SEE COMMENTS BELOW. | | | | | | 1) GARAGE POWER RISER SHOWS PANEL G1 BEING FED FROM | | | UTILITY TRANSFORMER. PANEL G1 IS DESCRIBED AS MLO TYPE. | | | PLEASE PROVIDE SERVICE EQUIPMENT DISCONNECT AND | | | OVERCURRENT PROTECTION TO COMPLY WITH NEC 230. | | | 2) SCOPE OF WORK IS LIMITED TO DETACHED GARAGE TYPE I | | | STRUCTURES. SITE LIGHTING, FIRE ALARM, AND LOW VOLTAGE | | | WORK REQUIRES SEPARATE PERMITS. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | SINCERELY, | | | | | | ENRIQUE QUINONEZ | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|