Plan Review Notes
Plan Review Notes For Permit 20100734
Permit Number 20100734
Review Stop P
Sequence Number 2
Notes
Date Text
2021-02-25 12:07:3002/25/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. DONE
  
 2. SECOND REQUEST, ON SHEET A2.1.1 FOR UNITS, 107/207,
 108/208, 109/209, AND 110/210 SHOW A SHOWER BUT SHEET
 P2.1.1 SHOWS TUBS PLEASE CLARIFY WHICH WILL BE USED AND
 MAKE CHANGES TO ALL OTHER FLOORS AS WELL PLEASE PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 NEW, THE DETAIL FOR THE SUMP PUMP REFERS TO P.6 WHICH
 THERE ARE TWO PAGE. PLEASE CORRECT AND ADD P 6.1.1 WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION.
  
 3. DONE
  
 4. STRIKE THROUGH ON SHEET A10.1.3 ANY SHOWERS CLEAR
 FLOOR SPACE NOT USED IN THIS BUILDING AND ANY OTHER
 DETAILS THAT DO NOT APPLY TO THIS BUILDING PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION.
  
 5. THIS COMMENT APPEARS NOT TO BE UPDATED ON THIS
 VERSION?ON SHEET A10.1.1 FOR UNIT A1 WITH THE TUB
 OPTION, IT SHALL HAVE THE CLEAR FLOOR SPACE TO THE SIDE
 OF THE VALVE ACCESS IN ACCORDANCE WITH THE PARALLEL
 APPROACH FHADM 7.53.
  
 6. NOTED AND CLARIFIED.
  
 7. DONE.
  
 8. PLEASE PLACE A NOTE THAT THE PERFORATED CAP CAN BE
 IN THE PLENUM OUT OF THE CAVITY OF THE WALL AND WITH
 THE MATERIAL THAT HAS A FLAME INDEX LIKE CPVC. THE AIR
 AD. VA IS NOT CLEAR?ON SHEET P5.1.1 FOR CONDENSATE AND
 PAN, IT HAS A PERFORATED CAP ON THE FOURTH FLOOR AND
 NOT VENT OR OUT THE WALL CAVITY PLEASE DETAIL OF A VENT
 THAT PROVIDES A FLOW OF AIR TO OR FROM A DRAINAGE
 SYSTEM, OR TO PROVIDE A CIRCULATION OF AIR WITHIN SUCH
 SYSTEM TO PROTECT TRAP SEALS FROM SIPHONAGE AND
 BACKPRESSURE PER THE 2017 FBC DEFINITIONS.
  
 9. DONE.
  
 10. DONE
  
 11. DONE.
  
 12. DONE.
  
 13. DONE.
  
 14. DONE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved