Plan Review Notes
Plan Review Notes For Permit 20100734
Permit Number 20100734
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2021-01-22 13:19:40FIRE PROVISO:
  
 1) ALL UNDERGROUND FIRE LINES SHALL BE INSTALLED UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS PER NFPA 24
  
  
 2) PER NFPA 101 CH 8
  
 8.6.11 CONCEALED SPACES AND DRAFTSTOPS.
 8.6.11.1 ANY CONCEALED COMBUSTIBLE SPACE IN WHICH
 BUILDING
 MATERIALS HAVING A FLAME SPREAD INDEX GREATER THAN
 CLASS A ARE
 EXPOSED SHALL BE DRAFTSTOPPED AS FOLLOWS:
  
 (2) EVERY UNOCCUPIED ATTIC SPACE SHALL BE SUBDIVIDED BY
 DRAFTSTOPS
 INTO AREAS NOT TO EXCEED 3000 FT2 (280 M2).
  
 REVIEW AND INSTALL AS APPLICABLE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]