Plan Review Notes
Plan Review Notes For Permit 20100734
Permit Number 20100734
Review Stop E
Sequence Number 2
Notes
Date Text
2021-01-29 16:30:57ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-3.1.1
  
 1) COMPLETED
  
 2) COMPLETED
  
 3) COMPLETED
  
  
 PAGE E-4.1.0
  
 1) NOTE #3 TO PANEL NOTES REFERENCES ROMEX IT IS NOT
 ALLOWED IN A TYPE 1 B BUILDING. 334.10 (5) UNLESS
 INSTALLED IN CONDUIT.
  
 GENERAL NOTES
  
 FIRE ALARM, BDA, SITE LIGHTING, LOW VOLTAGE WORK
 REQUIRES SEPARATE PERMITS.