| Plan Review Notes For Permit 20100734 |
| Permit Number |
20100734 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-01-29 16:30:57 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGE E-3.1.1 | | | | | | 1) COMPLETED | | | | | | 2) COMPLETED | | | | | | 3) COMPLETED | | | | | | | | | PAGE E-4.1.0 | | | | | | 1) NOTE #3 TO PANEL NOTES REFERENCES ROMEX IT IS NOT | | | ALLOWED IN A TYPE 1 B BUILDING. 334.10 (5) UNLESS | | | INSTALLED IN CONDUIT. | | | | | | GENERAL NOTES | | | | | | FIRE ALARM, BDA, SITE LIGHTING, LOW VOLTAGE WORK | | | REQUIRES SEPARATE PERMITS. |
|