| Date |
Text |
| 2020-11-18 16:09:24 | 11/18/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. ON SHEET C-172 THERE ARE BACKFLOW SHOWN WITH DETAILS |
| | AND COMMENTS PLEASE ADD THAT SEPARATE PERMITS ARE |
| | REQUIRED BY A LICENSED CONTRACTOR AND CERTIFIED BY THE |
| | CITY OF WEST PALM BEACH UTILITIES DEPARTMENT PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. ON SHEET A2.1.1 FOR UNITS, 107/207, 108/208, |
| | 109/209, AND 110/210 SHOW A SHOWER BUT SHEET P2.1.1 |
| | SHOWS TUBS PLEASE CLARIFY WHICH WILL BE USED AND MAKE |
| | CHANGES TO ALL OTHER FLOORS AS WELL PLEASE PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | 3. ON SHEET A10.1.1 AND A 10.1.2 PLEASE SHOW ALL CLEAR |
| | FLOOR SPACE DIMENSIONS FOR ALL AREAS PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION. |
| | |
| | 4. ON SHEET A10.1.3 PLEASE REMOVE SHOWERS CLEAR FLOOR |
| | SPACE NOT USED IN THIS BUILDING AND ANY OTHER DETAILS |
| | THAT DO NOT APPLY TO THIS BUILDING PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION. |
| | |
| | 5. ON SHEET A10.1.1 FOR UNIT A1 WITH THE TUB OPTION, IT |
| | SHALL HAVE THE CLEAR FLOOR SPACE TO THE SIDE OF THE |
| | VALVE ACCESS IN ACCORDANCE WITH THE PARALLEL APPROACH |
| | FHADM 7.53. |
| | |
| | 6. ON SHEET A10.1.1 PLEASE PROVIDE DETAIL FOR LAV |
| | HEIGHT THAT MEET THE REQUIREMENTS OF THE B BATHROOMS IN |
| | ACCORDANCE WITH THE FHADM 7.52. |
| | |
| | 7. ON SHEET P2.1.1 UNIT NEXT TO THE ELEVATOR MISSING A |
| | SANITARY DRAIN LINE FOR THE TUB AND THE SAME UNIT |
| | DIAGONALLY ACROSS PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | 8. ON SHEET P5.1.1 FOR CONDENSATE AND PAN, IT HAS A |
| | PERFORATED CAP ON THE FOURTH FLOOR AND NOT VENT OR OUT |
| | THE WALL CAVITY PLEASE DETAIL OF A VENT THAT PROVIDES A |
| | FLOW OF AIR TO OR FROM A DRAINAGE SYSTEM, OR TO PROVIDE |
| | A CIRCULATION OF AIR WITHIN SUCH SYSTEM TO PROTECT TRAP |
| | SEALS FROM SIPHONAGE AND BACKPRESSURE PER THE 2017 FBC |
| | DEFINITIONS. |
| | |
| | 9. ON SHEET P5.1.2 RISER 5 YOU HAVE A WASHING MACHINE |
| | ON A BATHROOM GROUP NOT ALLOWED PLEASE HAVE A SEPARATE |
| | STACK PER THE 2017 FBC SEC 912.2.1 HORIZONTAL WET VENT. |
| | |
| | 10. ON SHEET P5.1.3 PLEASE VALVE AT ACCESSIBLE |
| | LOCATIONS FOR WATER RISERS PER THE 2017 FBC SEC. 606.1 |
| | LOCATION OF FULL-OPEN VALVES. |
| | |
| | 11. SHEET P5.1.4; |
| | A. THERE ARE 5 WASHING MACHINES ON THE BATHROOM GROUP |
| | THAT IS NOT ALLOWED PLEASE HAVE A SEPARATE STACK PER |
| | THE 2017 FBC SEC 912.2.1 HORIZONTAL WET VENT. |
| | |
| | B. PLEASE LABEL ALL PIPE SIZES FOR SANITARY DRAINAGE |
| | BRANCHES PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | C. PLEASE SHOW TRAP PRIMER FOR FLOOR DRAIN AND GIVE |
| | PAGE REFERENCE FOR DETAIL PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | D. THE FLOOR DRAIN IS NOT VENTED PER THE 2017 FBC SEC. |
| | 901.2.1 VENTING REQUIRED. |
| | |
| | E. PLEASE PROVIDE PIPE SIZE FOR THE SUMP PUMP DRAINAGE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC. 107.5.1.3 (13) |
| | COMMERCIAL PLUMBING. |
| | |
| | 12. SHEET P5.1.5 PLEASE PROVIDE PIPE SIZING FOR THE |
| | WATER RISER REQUIRED PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.5.1.3 (13) COMMERCIAL PLUMBING. |
| | |
| | 13. SHEET P6.1.1 THERE IS THE DETAIL FOR THE HEATER |
| | PLEASE PROVIDE THE THERMAL EXPANSION DEVICE PER THE |
| | 2017 FBC SEC. FBC P 607.3. |
| | |
| | 14. ON SHEET P6.1.2 UNDER ELECTRIC WATER SOURCE |
| | SCHEDULE HAS A MIN EFF. OF 0.92 BUT ACCORDING TO NEACA |
| | HOT WATER REGULATION 2015 AND IT SHOULD BE AT EF 0.95. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |