2020-11-02 10:38:591ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100734
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE SHOW THAT ALL INTAKE OPENINGS MEET FBC M
 401.4
  
 2) PLEASE SHOW THAT ALL EXHAUST OUTLET LOCATIONS MEET
 FBC M 501.3.1
  
 3) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR NATURAL
 VENTILATION BASED ON FBC M 402
  
 4) SHEET M-4.1.1 NOTE 9 INDICATES A X VENT OUTSIDE AIR
 INTAKE, PLEASE PROVIDE SPECIFICATIONS FOR THIS AIR
 INTAKE. FBC M 401.5
  
 5) PLEASE PROVIDE A LETTER FROM THE DRYER MANUFACTURER
 STATING THAT THE X VENT DRYER EXHAUST TERMINATION IS
 ALLOWED WITH THEIR DRYER. THE X VENT IS UNIQUE IN THE
 FACT THAT IT USES BOTH THE BACK-DRAFT DAMPER AND THE
 LOUVER. THE INSTALLATION MANUAL DOES NOT ADDRESS THIS
 KIND OF INSTALLATION. WITH THE X VENT SYSTEM THE BOX OF
 THE X VENT IS MOUNTED INTO THE EXTERIOR OF THE WALL AND
 THE LOUVER IS FLUSH TO THE EXTERIOR WALL. THE EXHAUST
 OF THE DRYER MUST TRAVEL THROUGH THE EXHAUST DUCT, OPEN
 THE BACK-DRAFT DAMPER AND TRAVEL THROUGH THE X VENT
 COVER (LOUVER) BEFORE IT IS EXHAUSTED TO THE OUTDOORS.
 BECAUSE THIS PRODUCT USES BOTH THE BACK-DRAFT DAMPER
 AND THE OUTER COVER OF THE BOX (LOUVER) INSTEAD OF
 EITHER THE BACK-DRAFT DAMPER OR THE LOUVER THE DRYER
 MANUFACTURER MUST ADDRESS THE ASSEMBLY. WE MUST HAVE AN
 APPROVAL LETTER FROM THE SPECIFIC DRYER MANUFACTURER
 FOR THE SPECIFIC DRYER USED IN THIS PROJECT. FBC M
 504.8.4.2
  
 6) PLEASE SHOW THAT THE OUTER LOUVER OF THE X VENT
 COMPLIES WITH AMCA 550. FBC M 501.3.2
  
 7) PLEASE PROVIDE THE SPECIFICATIONS FROM THE
 MANUFACTURER OF THE X VENT THAT THE OUTER LOUVER MEETS
 MINIMUM AND MAXIMUM SIZES. FBC M 501.3.2
  
 8) PLEASE PROVIDE A DETAIL OF THE PATHWAY FROM THE 4TH
 FLOOR TO THE EQUIPMENT ON THE ROOF. FBC M 306.5
  
 9) PLEASE SHOW THAT THE EQUIPMENT ON THE ROOF COMPLIES
 FOR GUARD PROTECTION. FBC M 304.11
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  