2020-11-05 16:11:22ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-3.1.1
  
 1) HOUSE SERVICE SHOWS ONE SET OF 250 AL FOR 400A
  
 2) AIC RATING OF SERVICE AND PANELS REQUIRED PER 110.9,
 110,10
  
 3) MAIN #2 1400A REQUIRES COMPLIANCE WITH 240.87(A)(B)
 PLEASE INDICATE METHOD TO BE USED.
  
  
 PAGE E-4.1.0
  
 1) NOTE #3 TO PANEL NOTES REFERENCES ROMEX IT IS NOT
 ASLLOWED IN A TYPE 1 B BUILDING. 334.10 (5) UNLESS
 INSTALLED IN CONDUIT.
  
 GENERAL NOTES
  
 FIRE ALARM, BDA, SITE LIGHTING, LOW VOLTAGE WORK
 REQUIRES SEPARATE PERMITS.