Plan Review Notes
Plan Review Notes For Permit 20100734
Permit Number 20100734
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-06 10:52:52NEW 4 STORY APARTMENT BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected].
 CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) SURVEY PROVIDED SHOWS FLOOD ZONE "ABE" WHAT IS THAT?
 2) SURVEY PROVIDED NEEDS TO BE ELECTRONICALLY/DIGITALLY
 SIGNED BY THE SURVEYOR FOR USE IN PROJECTDOX.
 3) PLEASE SHOW ELEVATOR SIZE TO COMPLY WITH FBC 3002.4
 ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER.
 4) DRAWING (LS-0.1.0) SHOWS BUILDING CONSTRUCTION TYPE
 IIIB UNDER "PROJECT NARRATIVE" AND IB UNDER
 "CONSTRUCTION TYPE" PLEASE CLARIFY (CONSTRUCTION TYPE 1
 WOULD NEED TO SHOW ALL ROOF FRAMING AND SHEATHING TO BE
 FIRE RETARDANT PER FBC CHAPTER 6).
 5) DRAWING (LS-0.1.0) SHOULD ALSO SHOW THE HORIZONTAL
 FIRE SEPARATION REQUIREMENT PER FBC 420.3
 6) ACCESSIBILITY UNIT PLANS - MASTER BATH - PLEASE SHOW
 THE REQUIRED CLEAR FLOOR SPACE FOR THE DOORS THAT OPEN
 INTO THE BATHROOM FBC ACCESSIBILITY FHA REQUIREMENT 7
 (2)(B).
 7) DRAWING (S-6.1.1) SHOWS PER 2014 FBC - SHOULD BE
 2017 FBC.
 8) PLEASE SHOW THE UNIT DOOR NUMBER 1 ON THE DOOR
 SCHEDULE TO BE SELF-LATCHING AND CLOSING PER FBC
 716.5.9
 9) PLEASE SHOW THE SQUARE FOOTAGE OF THE BUILDING - PER
 FLOOR - TOTAL.
 10) DRAWING (A-2.1.3) PLEASE POINT OUT THE REQUIRED
 ROOF OVERFLOW SCUPPER LOCATIONS FBC 1503.4.1
 11) SOIL REPORT PROVIDED NEEDS TO BE
 ELECTRONICALLY/DIGITALLY SIGNED BY THE ENGINEER. SOIL
 REPORT IS BASED ON A 3-STORY BUILD IS THIS OK WITH YOU?
 12) DRAWING (A-10.1.2) IN THE "LEGEND FOR WALL
 REINFORCING" SAYS TO SEE DRAWING (A-10.4) THAT DRAWING
 IS NOT UPLOADED TO PROJECTDOX.
 13) A "THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF
 UNDERSTANDING" FORM WILL NEED TO BE FILLED OUT - PLEASE
 SEND AN EMAIL TO [email protected] AND ASK FOR "THE
 GUIDELINES AND POLICIES FOR THRESHOLD AND SPECIAL
 INSPECTORS"
 14) PLEASE PROVIDE A COPY OF THE FLOOR/CEILING SOUND
 TRANSMISSION REPORTS (IIC AND STC) AS NOTED ON THE
 DRAWINGS? - FBC1207
 15) DRAWING (S-2.1.6) HAS A STRAP CONNECTOR SCHEDULE -
 THE PLAN NEEDS TO SHOW THE LOCATION OF THE TRUSS
 CONNECTORS (STRAPPING).
 16) SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR -
 GAZEBOS, PARKING LOT, DUMPSTER ENCLOSURE, FENCE -
 PLEASE ACKNOWLEDGE THIS ON THE DRAWINGS.
 17) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD SHALL CONTAIN A STATEMENT THAT,
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA
 STATUTES.
  
  
  
  