| 2020-11-06 10:52:52 | NEW 4 STORY APARTMENT BUILDING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) SURVEY PROVIDED SHOWS FLOOD ZONE "ABE" WHAT IS THAT? |
| | 2) SURVEY PROVIDED NEEDS TO BE ELECTRONICALLY/DIGITALLY |
| | SIGNED BY THE SURVEYOR FOR USE IN PROJECTDOX. |
| | 3) PLEASE SHOW ELEVATOR SIZE TO COMPLY WITH FBC 3002.4 |
| | ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER. |
| | 4) DRAWING (LS-0.1.0) SHOWS BUILDING CONSTRUCTION TYPE |
| | IIIB UNDER "PROJECT NARRATIVE" AND IB UNDER |
| | "CONSTRUCTION TYPE" PLEASE CLARIFY (CONSTRUCTION TYPE 1 |
| | WOULD NEED TO SHOW ALL ROOF FRAMING AND SHEATHING TO BE |
| | FIRE RETARDANT PER FBC CHAPTER 6). |
| | 5) DRAWING (LS-0.1.0) SHOULD ALSO SHOW THE HORIZONTAL |
| | FIRE SEPARATION REQUIREMENT PER FBC 420.3 |
| | 6) ACCESSIBILITY UNIT PLANS - MASTER BATH - PLEASE SHOW |
| | THE REQUIRED CLEAR FLOOR SPACE FOR THE DOORS THAT OPEN |
| | INTO THE BATHROOM FBC ACCESSIBILITY FHA REQUIREMENT 7 |
| | (2)(B). |
| | 7) DRAWING (S-6.1.1) SHOWS PER 2014 FBC - SHOULD BE |
| | 2017 FBC. |
| | 8) PLEASE SHOW THE UNIT DOOR NUMBER 1 ON THE DOOR |
| | SCHEDULE TO BE SELF-LATCHING AND CLOSING PER FBC |
| | 716.5.9 |
| | 9) PLEASE SHOW THE SQUARE FOOTAGE OF THE BUILDING - PER |
| | FLOOR - TOTAL. |
| | 10) DRAWING (A-2.1.3) PLEASE POINT OUT THE REQUIRED |
| | ROOF OVERFLOW SCUPPER LOCATIONS FBC 1503.4.1 |
| | 11) SOIL REPORT PROVIDED NEEDS TO BE |
| | ELECTRONICALLY/DIGITALLY SIGNED BY THE ENGINEER. SOIL |
| | REPORT IS BASED ON A 3-STORY BUILD IS THIS OK WITH YOU? |
| | 12) DRAWING (A-10.1.2) IN THE "LEGEND FOR WALL |
| | REINFORCING" SAYS TO SEE DRAWING (A-10.4) THAT DRAWING |
| | IS NOT UPLOADED TO PROJECTDOX. |
| | 13) A "THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF |
| | UNDERSTANDING" FORM WILL NEED TO BE FILLED OUT - PLEASE |
| | SEND AN EMAIL TO [email protected] AND ASK FOR "THE |
| | GUIDELINES AND POLICIES FOR THRESHOLD AND SPECIAL |
| | INSPECTORS" |
| | 14) PLEASE PROVIDE A COPY OF THE FLOOR/CEILING SOUND |
| | TRANSMISSION REPORTS (IIC AND STC) AS NOTED ON THE |
| | DRAWINGS? - FBC1207 |
| | 15) DRAWING (S-2.1.6) HAS A STRAP CONNECTOR SCHEDULE - |
| | THE PLAN NEEDS TO SHOW THE LOCATION OF THE TRUSS |
| | CONNECTORS (STRAPPING). |
| | 16) SEPARATE PERMITS AND REVIEWS ARE REQUIRED FOR - |
| | GAZEBOS, PARKING LOT, DUMPSTER ENCLOSURE, FENCE - |
| | PLEASE ACKNOWLEDGE THIS ON THE DRAWINGS. |
| | 17) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD SHALL CONTAIN A STATEMENT THAT, |
| | TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA |
| | STATUTES. |
| | |
| | |
| | |
| | |