| 2020-12-08 10:52:30 | 3RD REVIEW: CORRECTED PLANS WERE NOT SUBMITTED. SEE 2ND |
| | REVIEW COMMENTS BELOW. |
| | 12/8/2020 |
| | |
| | 2ND REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100733 |
| | 12/4/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) BASED ON PIPE SIZING TABLE G2413.4(1) [402.4(2)] FBC |
| | RES. FUEL GAS THE 1/2 IN. SCHEDULE 40 GALVANIZED GAS |
| | PIPE IS UNDERSIZED TO SUPPLY THE 199,000 BTUH TANKLESS |
| | WATER HEATER. PLEASE PROVIDE A 3/4 IN. PIPE. |
| | |
| | 2) BASED ON PAGE 5 ON THE RHEEM WATER HEATER |
| | INSTALLATION MANUAL THE GAS INPUT PRESSURE RANGE IS |
| | 4.0- 10.5 IN. W.C. PLEASE PROVIDE A REGULATOR AT THE |
| | NEW WATER HEATER IN COMPLIANCE WITH SECTION G2421 FBC |
| | RES. SHOW THE MAKE AND MODEL OF THE REGULATOR ON THE |
| | PLAN AND SUBMIT SPECS MARKED UP OR HIGHLIGHTED TO THE |
| | SELECTED MODEL, INLET AND OUTLET PIPE SIZES AND |
| | PRESSURES, AND ORIFICE SIZE. SHOW THE REQUIRED PIPE |
| | UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR- |
| | SECTION 2421.2(7) FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |