| 2020-11-03 10:46:52 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100733 |
| | 11/3/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THIS IS A WATER |
| | HEATER REPLACEMENT HOWEVER I WAS UNABLE TO FIND A |
| | PREVIOUS PERMIT ON FILE FOR EITHER A GAS-FIRED TANKLESS |
| | OR STORAGE TYPE WATER HEATER. PLEASE PROVIDE THE |
| | FOLLOWING ITEMS FOR PERMITTING: |
| | |
| | A) A BASIC FLOOR PLAN SHOWING LOCATION OF THE NEW |
| | TANKLESS WATER HEATER. IT IS NOT CLEAR IF THE UNIT WILL |
| | BE INSTALLED IN THE INTERIOR OR EXTERIOR- SECTION |
| | 107.2.1 WPB. INDICATE THE MODEL NUMBER ON THE PLAN. |
| | |
| | B) GAS RISER DRAWING THAT INCLUDES ALL NEW AND EXISTING |
| | APPLIANCES, EQUIPMENT, AND ALL NEW AND EXISTING GAS |
| | PIPING FROM THE METER TO THE MOST REMOTE OUTLET- |
| | SECTIONS G2412.3, G2412.4, & G2413.2 FBC RES. PLEASE |
| | INCLUDE THE TYPES AND SIZES OF PIPING, BRANCH AND CUT |
| | PIPING LENGTHS, THE TOTAL AND INDIVIDUAL GAS LOADS IN |
| | BTUH, TOTAL DEVELOPED LENGTH OF THE SYSTEM, DELIVERY |
| | PRESSURE AT THE METER, LOCATIONS OF REGULATORS AND |
| | OUTLET PRESSURES- SECTIONS G2413.1, G2413.3, G2413.4.1, |
| | G2413.4.2, G2421.1 & G2421.2 FBC RES. |
| | |
| | C) INDICATE ON THE RISER THE PIPE SIZING TABLE USED PER |
| | TABLES G2413.4(1)- G2413.4(8) FBC RES. |
| | |
| | D) COMBUSTION AND VENTING PLANS ARE REQUIRED FOR |
| | INTERIOR GAS WATER HEATERS. FOR EXTERIOR INSTALLATIONS |
| | PLEASE PROVIDE AN ELEVATION DRAWING SHOWING THE |
| | REQUIRED CLEARANCES FOR THE UNIT PER MANUFACTURER?S |
| | SPECIFICATIONS- SECTIONS G2407.1, G2426.2, G2426.7, & |
| | G2448.1 FBC RES. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |