Plan Review Notes
Plan Review Notes For Permit 20100732
Permit Number 20100732
Review Stop B
Sequence Number 2
Notes
Date Text
2021-02-12 13:39:37PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 POOL PAVILION
 TYPE V-B CONSTRUCTION, UNSPRINKLERED
 GROUP A OCCUPANCY
  
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [PARTIALLY RESOLVED. THE DATE ON THE REVISED HAS A
 TYPO. THE DATE ON THE REVISED REPORT IS 1/19/20 AND IT
 SHOULD BE 1/19/21. A PRE-CONSTRUCTION ELEVATION
 CERTIFICATE IS REQUIRED TO BE SUBMITTED BEFORE THE
 PERMIT IS ISSUED. ALL OF THE POOL EQUIPMENT IS REQUIRED
 TO BE ELEVATED TO THE DFE (16' NAVD88), TO BE DRY FLOOD
 PROVED OR TO BE FLOOD WATER RESISTANT.] THIS PROJECT IS
 IN A SPECIAL FLOOD HAZARD AREA, AE. THE BFE IS 14'
 NAVD88 AND THE DFE IS 16' NAVD88. THE FINISH FLOOR
 ELEVATION OF THE POOL PAVILION IS SPECIFIED AS 15.2'
 NAVD88 PER THE PAVING AND GRADING PLAN. THIS IS BELOW
 THE REQUIRED DFE AND WILL BE REQUIRED TO BE DESIGNED TO
 COMPLY WITH FLOOD PROVISIONS OF THE FBC AND CITY OF
 WEST PALM BEACH FLOOD ORDINANCE. SHOW HOW THE BUILDING
 WILL COMPLY. IF DESIGNED FOR FLOOD WATERS TO FLOW
 THROUGH THE STRUCTURE ALL EQUIPMENT, CABINETS AND
 CONSTRUCTION MATERIALS THAT WILL BE BELOW DFE (16'
 NAVD) WITH HAVE TO BE ELEVATED OR OF MATERIALS THAT ARE
 RESISTANT TO WATER DAMAGE. SPECIFY THE PROPOSED
 ELEVATION OF THE FINISH FLOOR OF THE POOL PAVILION, IN
 NAVD 88 VERTICAL DATUM, ON THE ARCHITECTURAL PLANS. FBC
 1612
  
 2) RESOLVED.
  
 3) RESOLVED.
  
 4) RESOLVED.
  
 5) RESOLVED.
  
 6) RESOLVED.
  
 7) RESOLVED.
  
 8) [ PARTIALLY RESOLVED. ALTHOUGH THE FBC ACCESSIBILITY
 DOES NOT APPLY TO PRIVATE CLUBS AND POOLS, FAIR HOUSING
 REQUIREMENTS DO APPLY. SEE THE "FAIR HOUSING ACT DESIGN
 MANUAL" CHAPTER 2 ACCESSIBLE AND USABLE COMMON USE
 AREAS. SHOW THE ACCESSIBLE ROUTE TO AND INTO THE POOL
 PAVILION. CLARIFY THE LOCATION OF THE ACCESSIBLE
 ENTRANCE INTO THE PAVILION. IS THERE A RAMP? FBC
 107.2.1]
  
 9) A) [DEFERRED. ADDITIONAL INFORMATION IS REQUIRED TO
 BE SUBMITTED AND APPROVED BEFORE THE PRE-FAB FIREPLACE
 IS INSTALLED.] NOT ENOUGH INFORMATION IS PROVIDED FOR
 THE GAS FIREPLACE. IF IT IS A FACTORY BUILT UNIT
 PROVIDE THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS AND REQUIREMENTS. CITY
 AMENDMENTS FBC 107 & FBC 2111.14.1
  
 10) DEFERRED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, ROOF VENTS, SWING DOORS AND OVERHEAD
 GARAGE DOORS. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 11) DEFERRED. SUBMIT TRUSS DRAWINGS AND A TRUSS LAYOUT
 PLAN. FBC 2303.4 THESE ITEMS CAN BE DEFERRED IF
 REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND
 APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  