| 2021-02-12 13:39:37 | PLAN |
| | REVIEW COMMENTS |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | POOL PAVILION |
| | TYPE V-B CONSTRUCTION, UNSPRINKLERED |
| | GROUP A OCCUPANCY |
| | |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) [PARTIALLY RESOLVED. THE DATE ON THE REVISED HAS A |
| | TYPO. THE DATE ON THE REVISED REPORT IS 1/19/20 AND IT |
| | SHOULD BE 1/19/21. A PRE-CONSTRUCTION ELEVATION |
| | CERTIFICATE IS REQUIRED TO BE SUBMITTED BEFORE THE |
| | PERMIT IS ISSUED. ALL OF THE POOL EQUIPMENT IS REQUIRED |
| | TO BE ELEVATED TO THE DFE (16' NAVD88), TO BE DRY FLOOD |
| | PROVED OR TO BE FLOOD WATER RESISTANT.] THIS PROJECT IS |
| | IN A SPECIAL FLOOD HAZARD AREA, AE. THE BFE IS 14' |
| | NAVD88 AND THE DFE IS 16' NAVD88. THE FINISH FLOOR |
| | ELEVATION OF THE POOL PAVILION IS SPECIFIED AS 15.2' |
| | NAVD88 PER THE PAVING AND GRADING PLAN. THIS IS BELOW |
| | THE REQUIRED DFE AND WILL BE REQUIRED TO BE DESIGNED TO |
| | COMPLY WITH FLOOD PROVISIONS OF THE FBC AND CITY OF |
| | WEST PALM BEACH FLOOD ORDINANCE. SHOW HOW THE BUILDING |
| | WILL COMPLY. IF DESIGNED FOR FLOOD WATERS TO FLOW |
| | THROUGH THE STRUCTURE ALL EQUIPMENT, CABINETS AND |
| | CONSTRUCTION MATERIALS THAT WILL BE BELOW DFE (16' |
| | NAVD) WITH HAVE TO BE ELEVATED OR OF MATERIALS THAT ARE |
| | RESISTANT TO WATER DAMAGE. SPECIFY THE PROPOSED |
| | ELEVATION OF THE FINISH FLOOR OF THE POOL PAVILION, IN |
| | NAVD 88 VERTICAL DATUM, ON THE ARCHITECTURAL PLANS. FBC |
| | 1612 |
| | |
| | 2) RESOLVED. |
| | |
| | 3) RESOLVED. |
| | |
| | 4) RESOLVED. |
| | |
| | 5) RESOLVED. |
| | |
| | 6) RESOLVED. |
| | |
| | 7) RESOLVED. |
| | |
| | 8) [ PARTIALLY RESOLVED. ALTHOUGH THE FBC ACCESSIBILITY |
| | DOES NOT APPLY TO PRIVATE CLUBS AND POOLS, FAIR HOUSING |
| | REQUIREMENTS DO APPLY. SEE THE "FAIR HOUSING ACT DESIGN |
| | MANUAL" CHAPTER 2 ACCESSIBLE AND USABLE COMMON USE |
| | AREAS. SHOW THE ACCESSIBLE ROUTE TO AND INTO THE POOL |
| | PAVILION. CLARIFY THE LOCATION OF THE ACCESSIBLE |
| | ENTRANCE INTO THE PAVILION. IS THERE A RAMP? FBC |
| | 107.2.1] |
| | |
| | 9) A) [DEFERRED. ADDITIONAL INFORMATION IS REQUIRED TO |
| | BE SUBMITTED AND APPROVED BEFORE THE PRE-FAB FIREPLACE |
| | IS INSTALLED.] NOT ENOUGH INFORMATION IS PROVIDED FOR |
| | THE GAS FIREPLACE. IF IT IS A FACTORY BUILT UNIT |
| | PROVIDE THE MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS AND REQUIREMENTS. CITY |
| | AMENDMENTS FBC 107 & FBC 2111.14.1 |
| | |
| | 10) DEFERRED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT |
| | APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, ROOF VENTS, SWING DOORS AND OVERHEAD |
| | GARAGE DOORS. THESE ITEMS CAN BE DEFERRED IF REQUESTED, |
| | HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED |
| | BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE |
| | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 11) DEFERRED. SUBMIT TRUSS DRAWINGS AND A TRUSS LAYOUT |
| | PLAN. FBC 2303.4 THESE ITEMS CAN BE DEFERRED IF |
| | REQUESTED, HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND |
| | APPROVED BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE |
| | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR |
| | ELECTRONICALLY SUBMITTED DOCUMENTS. |
| | |
| | 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. |
| | |
| | |