Date Text
2020-12-01 17:33:1912/01/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE PROVIDE SPECIFICATION FOR TANK-LESS WATER
 HEATER PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. A SEPARATE PERMIT SHALL BE REQUIRED FOR THE BACKFLOW
 DEVICE PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1.
  
 3. THE ICEMAKER SHALL BE EQUIPPED WITH AN IN-LINE
 VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER THE
 2017 FBC SEC. 608.13.10.
  
 4. PLEASE PROVIDE A SHUT OFF VALVE FOR THE ICEMAKER AND
 MUST BE ACCESSIBLE FOR SHUTTING OFF WITHOUT MOVING
 UNITS, 2017 FBC SEC. R 2903.9.3 FIXTURE VALVES AND
 ACCESS. ACCESSIBLE SIGNIFIES ACCESS THAT REQUIRES THE
 REMOVAL OF AN ACCESS PANEL OR SIMILAR REMOVABLE
 OBSTRUCTION.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  