| 2020-12-01 17:33:19 | 12/01/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. PLEASE PROVIDE SPECIFICATION FOR TANK-LESS WATER |
| | HEATER PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. A SEPARATE PERMIT SHALL BE REQUIRED FOR THE BACKFLOW |
| | DEVICE PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 3. THE ICEMAKER SHALL BE EQUIPPED WITH AN IN-LINE |
| | VACUUM BREAKER THAT COMPLIES WITH ASSE 1024 PER THE |
| | 2017 FBC SEC. 608.13.10. |
| | |
| | 4. PLEASE PROVIDE A SHUT OFF VALVE FOR THE ICEMAKER AND |
| | MUST BE ACCESSIBLE FOR SHUTTING OFF WITHOUT MOVING |
| | UNITS, 2017 FBC SEC. R 2903.9.3 FIXTURE VALVES AND |
| | ACCESS. ACCESSIBLE SIGNIFIES ACCESS THAT REQUIRES THE |
| | REMOVAL OF AN ACCESS PANEL OR SIMILAR REMOVABLE |
| | OBSTRUCTION. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |