| Date |
Text |
| 2020-12-01 17:23:19 | 12/01/20 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE TABLE USED FOR SIZING PIPE REQUIRES 1? FOR THE 2 |
| | COOKING GRILL PLEASE PROVIDE A CORRECT TABLE AS THE |
| | BTU?S TOTAL 150 NOT 75 PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. THE DISTANCE FOR THE PIPE ON THE FIRE PLACE IS NOT |
| | LABEL PLEASE PROVIDE PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| | INSTALLED, OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| | AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| | THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| | EXTERIOR USE PER THE NFPA 58-11 SEC. 6.8.1.5. |
| | |
| | 4. PLEASE PROVIDE SPECIFICATION FOR GAS GRILLS AND |
| | DETAIL OF VENTING UNDER CABINET FORM MANUFACTURES |
| | SPECIFICATION PER THE 2017 FBC FG SEC.305.1. |
| | |
| | 5. PLEASE PROVIDE SPECIFICATION FOR FIRE PLACE PER THE |
| | 2017 FBC FG SEC.305.1. |
| | |
| | 6. PLEASE SHOW ALL UNIONS IN FRONT OF REGULATOR 1? OF |
| | EITHER SIDE PER THE 2017 FBC RES. SEC G2421.2 OR 2017 |
| | FBC FG SEC 410.2. |
| | |
| | 7. ON PPP-1 IT SHOWS THE LINES TO THE GRILLS ON 1/2? |
| | AND ON THE ISOMETRIC ON PPP-2 IT IS 3/4? PLEASE CORRECT |
| | AND RE0LABEL PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |