Plan Review Notes
Plan Review Notes For Permit 20100732
Permit Number 20100732
Review Stop E
Sequence Number 1
Notes
Date Text
2020-12-01 15:17:12ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGES EPP1 AND EPP2 ARE REVERSED IN THE SUBMITTED SET
 WHICH LABELS THEM WRONG.
  
 PAGE EPP 1
  
 RISER DIAGRAM AND PANEL SCHEDULE SHOW DIFFERENT TYPES
 OF WIRES FOR FEEDERS. AL AND CU.
  
 FAULT CURRENT CALCULATION NEEDED FOR SERICE AND PANEL
 110.9, 110,10
  
 INTERSYSTEM BONDING STRIP MIISING FROM SERVICE 250.94