| Plan Review Notes For Permit 20100732 |
| Permit Number |
20100732 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-12-01 15:17:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PAGES EPP1 AND EPP2 ARE REVERSED IN THE SUBMITTED SET | | | WHICH LABELS THEM WRONG. | | | | | | PAGE EPP 1 | | | | | | RISER DIAGRAM AND PANEL SCHEDULE SHOW DIFFERENT TYPES | | | OF WIRES FOR FEEDERS. AL AND CU. | | | | | | FAULT CURRENT CALCULATION NEEDED FOR SERICE AND PANEL | | | 110.9, 110,10 | | | | | | INTERSYSTEM BONDING STRIP MIISING FROM SERVICE 250.94 |
|