Plan Review Notes
Plan Review Notes For Permit 20100732
Permit Number 20100732
Review Stop B
Sequence Number 1
Notes
Date Text
2020-11-12 10:41:04PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
 POOL PAVILION
 TYPE V-B CONSTRUCTION, UNSPRINKLERED
 GROUP A OCCUPANCY
  
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS IN A SPECIAL FLOOD HAZARD AREA, AE.
 THE BFE IS 14' NAVD88 AND THE DFE IS 16' NAVD88. THE
 FINISH FLOOR ELEVATION OF THE POOL PAVILION IS
 SPECIFIED AS 15.2' NAVD88 PER THE PAVING AND GRADING
 PLAN. THIS IS BELOW THE REQUIRED DFE AND WILL BE
 REQUIRED TO BE DESIGNED TO COMPLY WITH FLOOD PROVISIONS
 OF THE FBC AND CITY OF WEST PALM BEACH FLOOD ORDINANCE.
 SHOW HOW THE BUILDING WILL COMPLY. IF DESIGNED FOR
 FLOOD WATERS TO FLOW THROUGH THE STRUCTURE ALL
 EQUIPMENT, CABINETS AND CONSTRUCTION MATERIALS THAT
 WILL BE BELOW DFE (16' NAVD) WITH HAVE TO BE ELEVATED
 OR OF MATERIALS THAT ARE RESISTANT TO WATER DAMAGE.
 SPECIFY THE PROPOSED ELEVATION OF THE FINISH FLOOR OF
 THE POOL PAVILION, IN NAVD 88 VERTICAL DATUM, ON THE
 ARCHITECTURAL PLANS. FBC 1612
  
 2) THE POOL AND DECK ARE REQUIRED TO HAVE SEPARATE
 PERMITS, APPLICATIONS, PLANS AND FEES. CITY AMENDMENTS
 FBC 105
  
 3) THE PROJECT NARRATIVE ON SHEET PP-1 REFERS TO
 PARKING SPACES AND A PARKING GARAGE. THIS PERMIT IS FOR
 THE POOL PAVILION THE GARAGE AND PARKING SPACES ARE
 UNDER SEPARATE PERMITS. PLEASE CORRECT. CITY AMENDMENTS
 FBC 107
  
 4) THE POOL PAVILION IS SPECIFIED ON PP-1 AS A GROUP U
 OCCUPANCY AND A STORAGE GARAGE IS SPECIFIED IN THE
 OCCUPANCY CLASSIFICATION TABLE. IT IS ACTUALLY A GROUP
 A-3 OCCUPANCY. FBC 303.4 PER THE DRAWINGS THE BUILDING
 IS 706 SQFT. AND WITH AN OCCUPANT LOAD FACTOR OF 15 NET
 PER TABLE 1004.5 THE OCCUPANT LOAD IS LESS THAN 50
 PEOPLE. FBC 303.1.1 SMALL BUILDINGS AND TENANT SPACES A
 BUILDING OR TENANT SPACE USED FOR ASSEMBLY PURPOSES
 WITH AN OCCUPANT LOAD OF LESS THAN 50 PERSONS SHALL BE
 CLASSIFIED AS A GROUP B OCCUPANCY. PLEASE CORRECT.
  
 5) THE LIFE SAFETY PLAN ON PP-1 COMBINES THE OCCUPANT
 CALCULATIONS FOR THE POOL PAVILION WITH THE POOL DECK.
 FOR CLARITY, PLEASE SEPARATE THE POOL PAVILION OCCUPANT
 CALCULATION FROM THE POOL DECK. CITY AMENDMENTS FBC 107
  
 6) THE LIFE SAFETY PLAN LEGEND HAS THE TRAVEL DISTANCE
 OF 200 FEET WITH AUTOMATIC FIRE SPRINKLERS. THIS
 STRUCTURE IS NOT SPRINKLERED. PLEASE CLARIFY. CITY
 AMENDMENTS FBC 107
  
 7) ON THE LIFE SAFETY PLAN IT APPEARS THAT ONE OF THE
 EXIT ACCESS ROUTES FROM THE POOL DECK GOES THROUGH A
 PART OF THE CLUBHOUSE. PLEASE CLARIFY. CITY AMENDMENTS
 FBC 107 & FBC CHAPTER 10
  
 8) SHOW THE REQUIRED PARKING SPACES, THE REQUIRED
 ACCESSIBLE SPACES AND THE ACCESSIBLE ROUTE FROM THE
 PARKING. FBC ACCESSIBILITY CHAPTERS 4 & 5
  
 9 A)NOT ENOUGH INFORMATION IS PROVIDED FOR THE GAS
 FIREPLACE. IF IT IS A FACTORY BUILT UNIT PROVIDE THE
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS AND REQUIREMENTS. CITY AMENDMENTS FBC 107
 & FBC 2111.14.1
 B) PROVIDE ADDITIONAL INFORMATION ON THE MASONRY
 FIREPLACE. CITY AMENDMENTS FBC 107 PROVIDE DRAWINGS AND
 DETAILS TO SHOW THAT IT COMPLIES WITH FBC 2111 AND
 2113.
  
 10) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, ROOF VENTS, SWING DOORS AND OVERHEAD
 GARAGE DOORS. THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 11) SUBMIT TRUSS DRAWINGS AND A TRUSS LAYOUT PLAN. FBC
 2303.4 THESE ITEMS CAN BE DEFERRED IF REQUESTED,
 HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED
 BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE
 INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR
 ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 12) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  