2021-02-16 17:00:59PLAN
 REVIEW COMMENTS
  
 CLUBHOUSE
 A-3 OCCUPANCY
 TYPE V-B, UN-SPRINKLERED
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PARTIALLY RESOLVED. [THE DATE OF THE REVISED
 GEOTECHINCAL REPORT IS 1/19/20 AND IT SHOULD BE
 1/19/21. ON SHEET OSP-1, THE NOTE UNDER FLOOD ZONE
 INFORMATION HAS FLOOD ZONE "ABE". PLEASE CORRECT.
 SUBMIT A PRE-CONSTRUCTION ELEVATION CERTIFICATE. NOTE:
 ALL EQUIPMENT THAT SERVICES THE BUILDING IS REQUIRED TO
 BE AT OR ABOVE 16' NAVD 88.] ACCORDING TO THE FLOOD
 INSURANCE RATE MAP WHICH WAS ADOPTED ON OCTOBER 5, 2017
 AND IS APPLICABLE TO THIS PROJECT, THE STRUCTURE IS IN
 AN AE FLOOD ZONE WHICH IS A SPECIAL FLOOD HAZARD AREA.
 THE FLOOD ZONE IS AE AND THE BFE IS 14' NAVD88. THE
 REQUIRED DFE IS 16' NAVD88. THE BUILDING AND ALL OF THE
 EQUIPMENT SERVICING IT ARE REQUIRED TO BE AT OR ABOVE
 THE DFE, 16' NAVD88. AS OF OCTOBER 5TH, 2017, THE CITY
 HAS ADOPTED NEW FLOOD INSURANCE RATE MAPS WHICH USE
 NAVD 88 AS THE VERTICAL DATUM. THE CITY ALSO ADOPTED A
 2' FREEBOARD WHICH REQUIRES THE FINISH FLOOR AND
 EQUIPMENT TO BE A MINIMUM OF TWO FEET ABOVE THE BFE.
 SPECIFY ALL ELEVATIONS IN NAVD 88. THREE ELEVATION
 CERTIFICATES ARE REQUIRED TO BE SUBMITTED. 1) A
 PRE-CONSTRUCTION ELEVATION CERTIFICATE BASED ON THE
 CONSTRUCTION PLANS IS REQUIRED BEFORE THE PERMIT IS
 ISSUED. 2) A BUILDING UNDER CONSTRUCTION ELEVATION
 CERTIFICATE WHEN FIRST FLOOR SLABS ARE POURED. 3) A
 FINISHED CONSTRUCTION ELEVATION WHEN THE JOB IS
 COMPLETE INCLUDING LANDSCAPING. THE FINAL ELEVATION
 CERTIFICATE IS REQUIRED TO BE SUBMITTED AND APPROVED
 BEFORE THE C.O. WILL BE ISSUED.
  
 2) RESOLVED. SPECIFY THE FINISH FLOOR ELEVATION ON THE
 ARCHITECTURAL PLANS. FBC 107.2.1
  
 3) RESOLVED. THE LIFE SAFETY LEGEND ON SHEET CH-LS-0.1
 HAS THE TRAVEL DISTANCE AS 200' FOR PROTECTED WITH
 AUTOMATIC FIRE SPRINKLERS. FBC TBL 1017.2 HAS 200' FOR
 NON-SPRINKLERED AND THIS BUILDING IS NOT SPRINKLERED.
 PLEASE CORRECT.
  
 4) RESOLVED. THE EXIT ACCESS TRAVEL DISTANCE FROM THE
 WORK ROOM SHOULD BE SHOWN FROM THE MOST REMOTE CORNER
 OF THE STORAGE ROOM. FBC 1017.3 MEASUREMENT. EXIT
 ACCESS TRAVEL DISTANCE SHALL BE MEASURED FROM THE MOST
 REMOTE POINT WITHIN A STORY ALONG THE NATURAL AND
 UNOBSTRUCTED PATH OF HORIZONTAL AND VERTICAL EGRESS
 TRAVEL TO THE ENTRANCE TO AN EXIT.
  
 5) RESOLVED. ON SHEET CH-LS-0.1, THE OCCUPANCY
 SEPARATION REQUIREMENTS SPECIFY FBC TBL. 508.4. THIS
 TABLE IS FOR SEPARATED OCCUPANCIES. SINCE YOU DO NOT
 SPECIFY AND FIRE RATED WALLS ON THE PLANS, IT APPEARS
 THAT YOU WISH TO USE NON-SEPARATED OCCUPANCIES. THE
 SECTION THAT WOULD APPLY TO THIS PROJECT WOULD BE FBC
 508.3 FOR NON-SEPARATED OCCUPANCIES.
  
 6) RESOLVED. THE BUILDING SECTIONS ON SHEET CH-2.2 ARE
 INCORRECTLY TAGGED AS BEING ON SHEET CH-3.2. THESE
 SECTION ARE ACTUALLY ON SHEET CH-3.3. PLEASE CORRECT.
  
 7) RESOLVED. PLEASE SHOW THE WHEEL CHAIR TURNING RADIUS
 SPACE IN THE BATHROOMS. FBC ACCESSIBILITY 304.3
  
 8) RESOLVED. SHOW THE REQUIRED ACCESSIBLE ACCESS TO THE
 EXERCISE EQUIPMENT. FBC ACCESSIBILITY 1004.1 CLEAR
 FLOOR SPACE. EXERCISE MACHINES AND EQUIPMENT SHALL HAVE
 A CLEAR FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR
 TRANSFER OR FOR USE BY AN INDIVIDUAL SEATED IN A
 WHEELCHAIR. CLEAR FLOOR OR GROUND SPACES REQUIRED AT
 EXERCISE MACHINES AND EQUIPMENT SHALL BE PERMITTED TO
 OVERLAP.
  
 9) RESOLVED. THE DOOR TO THE WORK ROOM DOES NOT APPEAR
 TO HAVE THE REQUIRED MINIMUM 18" ON THE PULL SIDE. FBC
 ACCESSIBILITY 404.2.4.1 SWINGING DOORS AND GATES SHALL
 HAVE MANEUVERING CLEARANCES COMPLYING WITH TABLE
 404.2.4.1.
  
 10) RESOLVED. SHOW COMPLIANCE WITH FBC 1210.2.2 WALLS
 AND PARTITIONS. WALLS AND PARTITIONS WITHIN 2 FEET (610
 MM) OF SERVICE SINKS, URINALS AND WATER CLOSETS SHALL
 HAVE A SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF NOT LESS THAN 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE MATERIALS USED IN
 SUCH WALLS SHALL BE OF A TYPE THAT IS NOT ADVERSELY
 AFFECTED BY MOISTURE.
  
 11) DEFERRED. FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT
 APPROVALS FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOWS (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES. THESE ITEMS CAN BE
 DEFERRED IF REQUESTED, HOWEVER, THE DOCUMENTS MUST BE
 SUBMITTED AND APPROVED BY THE BUILDING DEPARTMENT
 BEFORE THEY CAN BE INSTALLED. ONLY ONE SET IS REQUIRED
 TO BE UPLOADED FOR ELECTRONICALLY SUBMITTED DOCUMENTS.
  
 12) DEFERRED. FBC 107.3.4 SUBMIT TRUSS DRAWINGS, TRUSS
 LAYOUT PLANS, AND SHOP DRAWINGS FROM OTHER DELEGATE
 ENGINEERS FOR REVIEW.
  
 13) CORRECTION REQUIRED. [SHEET CH-LS-0.1 UNDER
 DEFERRED SUBMITTALS THERE ARE SOME ITEMS THAT ARE NOT
 CORRECT. THE DEFERRED SUBMITTALS CAN BE SUBMITTED TO
 THE BUILDING DEPARTMENT FOR REVIEW WITH THE PROPER
 SUBMITTAL FORM AS A NO FEE SUBMITTAL. THE ROOF COVERING
 WILL REQUIRE A ROOFING SUB-PERMIT THAT CAN BE APPLIED
 FOR AFTER THE ROOFING PRODUCT APPROVALS HAVE BEEN
 REVIEWED AND APPROVED BY THE BUILDING DEPARTMENT. THE
 WINDOWS, DOORS AND STOREFRONTS ARE COVERED UNDER THE
 BUILDING PERMIT AND DO NOT REQUIRE SEPARATE PERMITS.
 THE ONLY THING LISTED THAT REQUIRES A SEPARATE PERMIT
 IS THE LOW VOLTAGE.] FBC 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) RESOLVED. ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR INFORMATION PLEASE CONTACT: MS. SYBILLE WELTER, ART
 IN PUBLIC PLACES COORDINATOR AT 822-1515 OR E-MAIL:
 [email protected]
  
 15) RESOLVED. [THE CONSTRUCTION COSTS IN THE TAKEOFF
 THAT WAS PROVIDED OF $1,153,100.00 ONLY INCLUDES THE
 COSTS TO CONSTRUCT THE BUILDING.] IN ORDER TO AVOID
 PAYING DOUBLE, PLEASE PROVIDE A COST BREAK DOWN FOR THE
 ITEMS INCLUDED WITH THIS PERMIT THAT DO NOT REQUIRE
 SEPARATE PERMITS AND FEES. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 SWIMMING POOLS
 GENERATORS
 ALL OTHER ITEMS OTHER THAN BMEP
  
 16) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  