Plan Review Notes
Plan Review Notes For Permit 20100729
Permit Number 20100729
Review Stop M
Sequence Number 1
Notes
Date Text
2020-11-10 12:55:501ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100729
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE IDENTIFY THE ROOM NAMES THAT ARE USED FOR THE
 OUTDOOR AIR CALCULATIONS FOR AC-FIT1 & FIT2. PLEASE
 CALCULATE THE OUTDOOR AREA FOR THE WEIGHT ROOM AND
 AEROBICS ROOM USING THE NUMBERS PROVIDED UNDER (SPORTS
 AND AMUSEMENT) FBC M TABLE 403.3.1.1
  
 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THE
 ENTIRE BUILDING, PROVIDE OUTDOOR AIR CALCULATIONS BASED
 ON THE USE OF SPACE IN THIS BUILDING. FBC M TABLE
 403.3.1.1
  
 3) AC CLUB-2; SHEET MCH-3 INDICATES THE TOTAL AIR
 SUPPLY IS 1400 CFM. SHEET MCH-1 INDICATES THE TOTAL
 CFM?S IS 1,835. PLEASE SHOW WHERE THE DIFFERENCES ARE.
 FBC EC M403.2
  
 4) AC CLUB-1; SHEET MCH-3 INDICATES THE TOTAL AIR
 SUPPLY IS 1400 CFM. SHEET MCH-1 INDICATES THE TOTAL
 CFM?S IS 1800. PLEASE SHOW WHERE THE DIFFERENCES ARE.
 FBC EC M403.2
  
 5) SHEET MCH-1; UNITS AC-1 AND AC-CLUB2 APPEAR TO HAVE
 A RETURN COMING FROM THE A/V CLOSET. PLEASE SHOW HOW
 THIS WOULD MEET FBC M 601.5 (7)
  
 6) SHEET MCH-3 INDICATES THAT EF-1 HAS A TOTAL EXHAUST
 CFM RATE OF 50 AND IS CONTROLLED BY A LIGHT SWITCH.
 THIS WOULD NOT COMPLY WITH FBC M TABLE 403.3.1.1 (NOTE
 E)
  
 7) SHEET MCH-1 PLEASE SHOW CFM?S FOR THE SUPPLY AIR IN
 THE A/V CLOSET. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved