| 2020-11-10 12:55:50 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20100729 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE IDENTIFY THE ROOM NAMES THAT ARE USED FOR THE |
| | OUTDOOR AIR CALCULATIONS FOR AC-FIT1 & FIT2. PLEASE |
| | CALCULATE THE OUTDOOR AREA FOR THE WEIGHT ROOM AND |
| | AEROBICS ROOM USING THE NUMBERS PROVIDED UNDER (SPORTS |
| | AND AMUSEMENT) FBC M TABLE 403.3.1.1 |
| | |
| | 2) PLEASE PROVIDE OUTDOOR AIR CALCULATIONS FOR THE |
| | ENTIRE BUILDING, PROVIDE OUTDOOR AIR CALCULATIONS BASED |
| | ON THE USE OF SPACE IN THIS BUILDING. FBC M TABLE |
| | 403.3.1.1 |
| | |
| | 3) AC CLUB-2; SHEET MCH-3 INDICATES THE TOTAL AIR |
| | SUPPLY IS 1400 CFM. SHEET MCH-1 INDICATES THE TOTAL |
| | CFM?S IS 1,835. PLEASE SHOW WHERE THE DIFFERENCES ARE. |
| | FBC EC M403.2 |
| | |
| | 4) AC CLUB-1; SHEET MCH-3 INDICATES THE TOTAL AIR |
| | SUPPLY IS 1400 CFM. SHEET MCH-1 INDICATES THE TOTAL |
| | CFM?S IS 1800. PLEASE SHOW WHERE THE DIFFERENCES ARE. |
| | FBC EC M403.2 |
| | |
| | 5) SHEET MCH-1; UNITS AC-1 AND AC-CLUB2 APPEAR TO HAVE |
| | A RETURN COMING FROM THE A/V CLOSET. PLEASE SHOW HOW |
| | THIS WOULD MEET FBC M 601.5 (7) |
| | |
| | 6) SHEET MCH-3 INDICATES THAT EF-1 HAS A TOTAL EXHAUST |
| | CFM RATE OF 50 AND IS CONTROLLED BY A LIGHT SWITCH. |
| | THIS WOULD NOT COMPLY WITH FBC M TABLE 403.3.1.1 (NOTE |
| | E) |
| | |
| | 7) SHEET MCH-1 PLEASE SHOW CFM?S FOR THE SUPPLY AIR IN |
| | THE A/V CLOSET. FBC 107.2.1 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |