Plan Review Notes
Plan Review Notes For Permit 20100729
Permit Number 20100729
Review Stop E
Sequence Number 1
Notes
Date Text
2020-11-25 16:51:38CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED.
  
 1) PLEASE SHOW LOCATION OF PANEL M. IS THIS PANEL
 WITHIN THE CLUBHOUSE OR LOCATED DETACHED FROM THE
 STRUCTURE? FCB 107
 2) GROUNDING ELECTRODE CONDUCTOR FROM METER TO PANEL CH
 IS TOO SMALL. IT SHOULD BE BASED ON THE EQUIVALENT SIZE
 OF 1000 KCMIL (2 SETS OF 4#500 KCMIL AL), TABLE 250.66
 NEC
 3) RISER DIAGRAM SHOWS PANEL M WITH A GROUND CONNECTED
 TO THE GROUNDING SYSTEM FOR MAIN SERVICE. IF PANEL M IS
 LOCATED ON A DETACHED STRUCTURE, THEN IT NEEDS TO BE
 GROUNDED AS PER NEC 250.32 WITH ITS OWN GROUNDING
 ELECTRODE AND GROUNDING ELECTRODE CONDUCTOR. IF PANEL M
 IS LOCATED WITHIN THE CLUBHOUSE STRUCTURE IT NEEDS TO
 BE GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR AS
 PART OF THE FEEDER FROM PANEL CH. NEC TABLE 250.66, NEC
 250.32.
 4) PLEASE SHOW FEEDER SIZE (INCLUDE GROUNDING EQUIPMENT
 CONDUCTOR) FROM PANEL CH TO PANEL M. FCB 107
 5) PANEL M IS SHOWN AS MLO ON PANEL SCHEDULE, BUT RISER
 DIAGRAM INDICATES A 200 A MCB. PLEASE CORRECT
 DISCREPANCIES. FCB 107
 6) PANEL SCHEDULE CH DOES NOT HAVE INFORMATION ON
 BREAKER SIZE AND FEEDER FOR PANEL M AND THIS
 INFORMATION IS NOT PROVIDED ON RISER DIAGRAM. FCB 107
 7) PANEL CH: PLEASE INCLUDE WIRE (INCLUDING GROUNDING
 EQUIPMENT CONDUCTOR), CONDUIT SIZES, BREAKER SIZES FOR
 ALL CH UNITS. CONDUCTORS CAN BE INDICATED ON POWER PLAN
 IF MORE CONVENIENT. FCB 107
 8) PANEL SCHEDULE M: PLEASE INCLUDE WIRE AND CONDUIT
 SIZES (INCLUDING GROUNDING EQUIPMENT CONDUCTOR) FOR ALL
 AC AND CU UNITS. CONDUCTORS CAN BE INDICATED ON POWER
 PLAN TOO IF MORE CONVENIENT. FCB 107
 9) PLEASE SUBMIT SHORT CIRCUIT CALCULATIONS AND
 AVAILABLE FAULT CURRENTS FOR PANELS CH AND M NEC 110.24
 10) PANEL SCHEDULE M HAS A NOTE SHOWING A PANEL PV
 CALCULATION. THIS PANEL IS NOT SHOWN ANYWHERE ELSE AND
 IS NOT PART OF THE RISER DIAGRAM. THIS LOAD IS NOT
 INCLUDED IN ANY OF THE LOAD CALCULATIONS EITHER. PLEASE
 CLARIFY. FCB 107
 11) PLEASE SEE COMMENTS FROM BUILDING REVIEWER
 REGARDING STRUCTURE BEING ON A SPECIAL FLOOD ZONE AND
 REQUIREMENTS FOR EQUIPMENT LOCATION.
  
  
 END OF COMMENTS.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  