| 2020-11-25 16:51:38 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | REVIEW STATUS: FAILED. |
| | |
| | 1) PLEASE SHOW LOCATION OF PANEL M. IS THIS PANEL |
| | WITHIN THE CLUBHOUSE OR LOCATED DETACHED FROM THE |
| | STRUCTURE? FCB 107 |
| | 2) GROUNDING ELECTRODE CONDUCTOR FROM METER TO PANEL CH |
| | IS TOO SMALL. IT SHOULD BE BASED ON THE EQUIVALENT SIZE |
| | OF 1000 KCMIL (2 SETS OF 4#500 KCMIL AL), TABLE 250.66 |
| | NEC |
| | 3) RISER DIAGRAM SHOWS PANEL M WITH A GROUND CONNECTED |
| | TO THE GROUNDING SYSTEM FOR MAIN SERVICE. IF PANEL M IS |
| | LOCATED ON A DETACHED STRUCTURE, THEN IT NEEDS TO BE |
| | GROUNDED AS PER NEC 250.32 WITH ITS OWN GROUNDING |
| | ELECTRODE AND GROUNDING ELECTRODE CONDUCTOR. IF PANEL M |
| | IS LOCATED WITHIN THE CLUBHOUSE STRUCTURE IT NEEDS TO |
| | BE GROUNDED WITH AN EQUIPMENT GROUNDING CONDUCTOR AS |
| | PART OF THE FEEDER FROM PANEL CH. NEC TABLE 250.66, NEC |
| | 250.32. |
| | 4) PLEASE SHOW FEEDER SIZE (INCLUDE GROUNDING EQUIPMENT |
| | CONDUCTOR) FROM PANEL CH TO PANEL M. FCB 107 |
| | 5) PANEL M IS SHOWN AS MLO ON PANEL SCHEDULE, BUT RISER |
| | DIAGRAM INDICATES A 200 A MCB. PLEASE CORRECT |
| | DISCREPANCIES. FCB 107 |
| | 6) PANEL SCHEDULE CH DOES NOT HAVE INFORMATION ON |
| | BREAKER SIZE AND FEEDER FOR PANEL M AND THIS |
| | INFORMATION IS NOT PROVIDED ON RISER DIAGRAM. FCB 107 |
| | 7) PANEL CH: PLEASE INCLUDE WIRE (INCLUDING GROUNDING |
| | EQUIPMENT CONDUCTOR), CONDUIT SIZES, BREAKER SIZES FOR |
| | ALL CH UNITS. CONDUCTORS CAN BE INDICATED ON POWER PLAN |
| | IF MORE CONVENIENT. FCB 107 |
| | 8) PANEL SCHEDULE M: PLEASE INCLUDE WIRE AND CONDUIT |
| | SIZES (INCLUDING GROUNDING EQUIPMENT CONDUCTOR) FOR ALL |
| | AC AND CU UNITS. CONDUCTORS CAN BE INDICATED ON POWER |
| | PLAN TOO IF MORE CONVENIENT. FCB 107 |
| | 9) PLEASE SUBMIT SHORT CIRCUIT CALCULATIONS AND |
| | AVAILABLE FAULT CURRENTS FOR PANELS CH AND M NEC 110.24 |
| | 10) PANEL SCHEDULE M HAS A NOTE SHOWING A PANEL PV |
| | CALCULATION. THIS PANEL IS NOT SHOWN ANYWHERE ELSE AND |
| | IS NOT PART OF THE RISER DIAGRAM. THIS LOAD IS NOT |
| | INCLUDED IN ANY OF THE LOAD CALCULATIONS EITHER. PLEASE |
| | CLARIFY. FCB 107 |
| | 11) PLEASE SEE COMMENTS FROM BUILDING REVIEWER |
| | REGARDING STRUCTURE BEING ON A SPECIAL FLOOD ZONE AND |
| | REQUIREMENTS FOR EQUIPMENT LOCATION. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |