| 2021-06-29 14:34:14 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 20100727 |
| | 6/29/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET C154: SHOW THE WATER LINE CONNECTION TO THE |
| | TRASH COMPACTOR HOSE BIB- SECTION 107.2.1 WPB. |
| | |
| | 2) SHEETS PTC-1 & C-144: REFER TO SEC. 90-203 & 90.205 |
| | CITY OF WEST PALM BEACH CODE OR ORDINANCES. BASED ON |
| | THE SECTIONS LISTED IT DOES NOT APPEAR THAT THE |
| | DISCHARGES FROM THE TRASH COMPACTOR AND DUMPSTER DRAINS |
| | MEET THE EXCEPTIONS OF ALLOWABLE SUBSTANCES TO BE |
| | DISCHARGED INTO THE CITY STORMWATER SYSTEM. IT APPEARS |
| | THE DISCHARGES FROM THE DRAINS MUST BE CONNECTED TO THE |
| | CITY SANITARY SYSTEM, AND MAY REQUIRE AN INTERCEPTOR |
| | DEPENDING ON THE TYPE OF WASTE WATER BEING DISCHARGED- |
| | SECTION 1003.1 FBC P. THE PLANS ALSO INDICATE POSSIBLE |
| | STORM WATER CONTAMINATION FROM THE DUMP TRUCK THAT WILL |
| | BE ACCESSING THE COMPACTOR AND DUMPSTER AREA. FOR |
| | FURTHER INFORMATION PLEASE CONTACT THE CITY OF WEST |
| | PALM BEACH UTILITIES DEPT. STORMWATER DRAINAGE DIVISION |
| | AT 561-822-2185. |
| | |
| | 3) PTC-1: NONPOTABLE WATER OUTLET SIGNAGE AT THE HOSE |
| | BIB, AND COLOR MARKING OF THE NON-POTABLE WATER PIPING |
| | ARE REQUIRED. PLEASE REVIEW THE FBC P CODE SECTIONS |
| | LISTED BELOW AND PROVIDE DETAILS AND NOTES ON THE PLAN. |
| | |
| | 608.8 IDENTIFICATION OF NONPOTABLE WATER SYSTEMS. |
| | WHERE NONPOTABLE WATER SYSTEMS ARE INSTALLED, THE |
| | PIPING CONVEYING THE NONPOTABLE WATER SHALL BE |
| | IDENTIFIED EITHER BY COLOR MARKING, METAL TAGS OR TAPE |
| | IN ACCORDANCE WITH SECTIONS 608.8.1 THROUGH 608.8.2.3. |
| | |
| | 608.8.1SIGNAGE REQUIRED. |
| | NONPOTABLE WATER OUTLETS, SUCH AS HOSE CONNECTIONS, |
| | OPEN ENDED PIPES AND FAUCETS, SHALL BE IDENTIFIED WITH |
| | SIGNAGE THAT READS AS FOLLOWS: ?NONPOTABLE WATER IS |
| | UTILIZED FOR [APPLICATION NAME]. CAUTION: NONPOTABLE |
| | WATER ? DO NOT DRINK.? THE WORDS SHALL BE LEGIBLY AND |
| | INDELIBLY PRINTED ON A TAG OR SIGN CONSTRUCTED OF |
| | CORROSION-RESISTANT WATERPROOF MATERIAL OR SHALL BE |
| | INDELIBLY PRINTED ON THE FIXTURE. THE LETTERS OF THE |
| | WORDS SHALL BE NOT LESS THAN 0.5 INCH IN HEIGHT AND IN |
| | COLORS IN CONTRAST TO THE BACKGROUND ON WHICH THEY ARE |
| | APPLIED. IN ADDITION TO THE REQUIRED WORDAGE, THE |
| | PICTOGRAPH SHOWN IN FIGURE 608.8.1 SHALL APPEAR ON THE |
| | REQUIRED SIGNAGE. |
| | |
| | 608.8.2 DISTRIBUTION PIPE LABELING AND MARKING. |
| | NONPOTABLE DISTRIBUTION PIPING SHALL BE PURPLE IN COLOR |
| | AND SHALL BE EMBOSSED, OR INTEGRALLY STAMPED OR MARKED, |
| | WITH THE WORDS: ?CAUTION: NONPOTABLE WATER ? DO NOT |
| | DRINK? OR THE PIPING SHALL BE INSTALLED WITH A PURPLE |
| | IDENTIFICATION TAPE OR WRAP. PIPE IDENTIFICATION SHALL |
| | INCLUDE THE CONTENTS OF THE PIPING SYSTEM AND AN ARROW |
| | INDICATING THE DIRECTION OF FLOW. HAZARDOUS PIPING |
| | SYSTEMS SHALL ALSO CONTAIN INFORMATION ADDRESSING THE |
| | NATURE OF THE HAZARD. PIPE IDENTIFICATION SHALL BE |
| | REPEATED AT INTERVALS NOT EXCEEDING 25 FEET (7620 MM) |
| | AND AT EACH POINT WHERE THE PIPING PASSES THROUGH A |
| | WALL, FLOOR OR ROOF. LETTERING SHALL BE READILY |
| | OBSERVABLE WITHIN THE ROOM OR SPACE WHERE THE PIPING IS |
| | LOCATED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |