| 2022-10-04 16:46:20 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT-20100709 |
| | 10/4/24 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET AE410 DETAILS A1 & B1: SHOW THE DEPTH AND |
| | WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACES AT THE |
| | ACCESSIBLE WATER CLOSETS, LAVATORIES, AND URINAL- SECS. |
| | 604.3, 606.2 & 605.3 FBC ACC. |
| | |
| | 2) AE410- A1: THE COMPARTMENT DOOR SHALL NOT SWING INTO |
| | THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORY- SEC. |
| | 603.2.3 FBC ACC. |
| | |
| | 3) AE410- D2: THE TILE BACKER AT THE MOP SINK SHALL |
| | EXTEND 4FT. ABOVE THE SINK- SEC. 1210.2.2 FBC B. |
| | |
| | 4) P-111 & P-201: A GREASE INTERCEPTOR IS REQUIRED TO |
| | RECEIVE THE GREASE LADEN DRAINAGE FROM THE |
| | 3-COMPARTMENT SINK, THE MOP SINK, DISHWASHER, AND ANY |
| | OTHER SINKS, FLOOR DRAINS ETC. DISCHARGING GREASE LADEN |
| | WASTE- SEC. 1003.3.1 FBC P. REVISE THE PLANS TO SHOW |
| | THE LOCATION OF THE INTERCEPTOR AND PLUMBING PIPING |
| | DETAILS- SEC. 107.2.1 WPB. |
| | PLEASE NOTE A SEPARATE PERMIT IS REQUIRED FOR |
| | INSTALLATION OF THE INTERCEPTOR AND DUE TO A RECENT |
| | CHANGE IN PROCESS, THE INTERCEPTOR PERMIT IS REQUIRED |
| | TO BE SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY |
| | PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE |
| | DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY |
| | EMAILING A COMPLETED PERMIT APPLICATION TO |
| | [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| | CHANGE THE REVIEW STATUS TO PASS. |
| | |
| | 5) P-200: AN ACCESSIBLE SHOWER (SH-1) IS SHOWN IN THE |
| | FIXTURE SCHEDULE HOWEVER THE LOCATION OF THE FIXTURE |
| | AND PIPING DETAILS ARE NOT SHOWN IN THE PLANS- SEC. |
| | 1`07.2.1 WPB. |
| | |
| | 6) P-111 & P-201: SHOW HOW TEMPERED WATER WILL BE |
| | DELIVERED FROM THE PUBLIC LAVATORIES- SEC. 419.5 FBC P. |
| | |
| | 7) P-111 & P-201: THE HW RECIRCULATION LOOP IS NOT |
| | DESIGNED IN COMPLIANCE WITH SEC. C404.5.1 FBC EC. THE |
| | 1/2-INCH HW PIPES TO THE LAVATORIES ARE EXCEEDING THE |
| | MAXIMUM ALLOWABLE 2 FT. LENGTHS FROM THE HOT WATER |
| | SOURCE (RECIRCULATION LINE) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |