| Plan Review Notes For Permit 20100709 |
| Permit Number |
20100709 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2021-10-20 10:08:57 | EXTERIOR COOLER | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) CODE IN EFFECT HAS CHANGED ON 1/1/21 - PLEASE REVISE | | | THE DRAWINGS TO SHOW THE CODE IN EFFECT (2020 FBC USING | | | ASCE 7-16) | | | 2) PLEASE SHOW THE TERMITE PREVENTION REQUIRED FOR THE | | | NEW STRUCTURE - FBC 1816 | | | 3) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVAL FOR THE EXTERIOR DOORS - ALL PRODUCT | | | APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY | | | THE DESIGNER OF RECORD FBC WPB 107.3.4 | | | 4) DRAWING S004 SHOULD SHOW THE RISK CATEGORY USED FOR | | | WIND DESIGN FBC 1603.1.4 - SHOW THE CORRECT WIND SPEED | | | USED FOR THE WIND DESIGN BASED ON THE RISK CATEGORY PER | | | FBC WPB SECTION 120. | | | 5) PLEASE PROVIDE THE COOLER WALL AND ROOF PANEL | | | DETAILS - DESCRIPTION OF WALL PANELS, ATTACHMENTS TO | | | FOUNDATION, ATTACHMENTS OF PANEL TO PANEL ETC. TO | | | COMPLY WITH THE WIND LOADS SHOWN ON DRAWING S004. |
|