Plan Review Notes
Plan Review Notes For Permit 20100659
Permit Number 20100659
Review Stop M
Sequence Number 1
Notes
Date Text
2020-10-27 09:58:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT-20100659
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A-2 INDICATES THE AHU WILL BE RELOCATED AS
 SHOWN ON REMODELED PLAN. THE REMODELED PLAN DOES NOT
 SHOW THE AHU. PLEASE PROVIDE A MECHANICAL DRAWING
 SHOWING THE LOCATION AND DUCT WORK. FBC 107.2
  
 2) PLEASE PROVIDE AN ENERGY CALCULATION. FBC EC
 R101.5.1.1.2
  
 3) PLEASE PROVIDE THE MANUAL J CALCULATION FOR
 MECHANICAL SYSTEM USED FOR THE NEW ADDITION. FBC RES
 M1401.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  