| 2020-10-27 14:15:40 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100549 |
| | 10/27/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) LP GAS TANK AND INSTALLATION SPECS HAVE BEEN |
| | INCORRECTLY SUBMITTED. PLEASE PROVIDE A NATURAL GAS |
| | SUBMITTAL PACKAGE THAT INCLUDES THE GENERATOR FLEX |
| | CONNECTOR, REGULATOR, AND PIPE SIZING TABLES- SECTION |
| | 107.2.1 WPB. |
| | |
| | 2) GAS RISER DRAWING: PLEASE INCLUDE THE 22,000 BTUH |
| | DRYER IN THE EXISTING APPLIANCE LIST, AND CORRECT THE |
| | BTUH LOAD TOTAL TO INDICATE 869,000 BTUH. THE DRYER WAS |
| | INCLUDED WITH THE APPROVED PLANS UNDER PERMIT- |
| | 99100191- SECTIONS G2412.3, G2412.4 & G2413.2 FBC RES. |
| | |
| | A) INDICATE THE RISER PIPE SIZES AT THE METER- SECTION |
| | G2413.1 FBC RES. PLEASE NOTE THE PIPE SIZING TABLE |
| | 402.4(3) FBC FG YOU SHOW ON THE RISER INDICATES A |
| | MINIMUM 1-1/4 IN. MAIN SUPPLY PIPE IS REQUIRED FOR A |
| | 869,000 BTUH SYSTEM AT A TOTAL DEVELOPED LENGTH OF 110 |
| | FT. |
| | |
| | B) A REGULATOR AT THE GENERATOR IS REQUIRED TO DROP THE |
| | PRESSURE TO 3.5- 7 IN. W.C PER THE GENERATOR SPECS- |
| | SECTION 2421.1 FBC RES. SHOW THE REGULATOR ON THE RISER |
| | AND THE REQUIRED PIPE UNIONS PER SECTION 2421.2(7) FBC |
| | RES. SUBMIT MANUFACTURER?S SPECIFICATIONS MARKED UP OR |
| | HIGHLIGHTED TO SHOW THE SELECTED MODEL, INPUT AND |
| | OUTPUT PIPE SIZE AND PRESSURE, AND ORIFICE SIZE. |
| | |
| | 2) CORRECT THE SURVEY DRAWING TO INDICATE A 10 FT. |
| | CLEARANCE FOR THE GENERATOR TO MECHANICAL AND GRAVITY |
| | AIR INTAKES (OPERABLE WINDOWS AND DOORS) INTO THE |
| | RESIDENCE- SECTION R303.5.1 FBC RES. |
| | |
| | 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |