| 2020-10-14 13:03:19 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT- 20100534 |
| | 10/14/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A1.1.1: REFER TO SECTIONS 306, 307, AND 602 |
| | FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| | DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| | CLEARANCES, SPOUT HEIGHTS, SPOUT LOCATIONS, AND THE ADA |
| | BARRIERS. |
| | |
| | 2) P0.1 & P2.1: RELOCATING THE DRINKING FOUNTAIN DRAIN |
| | MAY REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO |
| | LOCATE REINFORCING STEEL OR POST STRESSED FLOOR |
| | TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO VERIFY |
| | COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | A) THE NEW DRAIN PIPE PENETRATION OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION |
| | 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |