2020-10-20 12:14:531ST REVIEW FBC-2017 RES.
 PERMIT-20100525
 10/20/2020
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1.1: PLEASE PROVIDE A PLUMBING SCOPE OF WORK
 OUTLINE ON THE PLAN. IT APPEARS A NEW LAUNDRY ROOM AND
 BATHROOM ARE BEING CONSTRUCTED, AND FIXTURES ARE BEING
 REPLACED IN EXISTING BATHROOMS ETC. PLEASE CLARIFY BY
 PROVIDING AN ITEMIZED LIST OF PROPOSED WORK- SECTION
 107.2.1 WPB.
  
 2) SHEET P1.1: PROVIDE SANITARY RISER DRAWINGS FOR THE
 WASHING MACHINE IN THE MAIN HOUSE, AND THE LAVATORY IN
 THE GUEST SUITE- SECTION 107.3.5.3 WPB.
  
 3) P1.1: SHOW CLEANOUTS AT THE BASE OF THE STACKS
 SERVING THE NEW 2ND FLOOR BATHROOM AND THE WASHING
 MACHINE- SECTION P3005.2.4 FBC RES.
  
 4) P1.1 PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER
 HEATER AND SUBMIT MANUFACTURER'S SPECIFICATIONS- TABLE
 C404.2 FBC EC AND G2448.1 FBC RES. PLEASE NOTE A
 SEPARATE PERMIT IS REQUIRED FOR THE GAS PIPING
 INSTALLATION TO THE WATER HEATER AND ALL OTHER GAS
 FIRED APPLIANCES- SECTION 107.2.1 WPB.
  
 5) P1.1: PROVIDE GAS VENTING DIAGRAM FOR THE WATER
 HEATER SHOWING THE TYPE AND SIZE OF VENT PIPE, THE
 TOTAL RUN LENGTH OF THE VENTING AND TERMINATION HEIGHT
 ABOVE THE ROOF- SECTION G2448.1 AND G2426 FBC RES.
 PLEASE NOTE THE VENTING PLAN CAN BE SUBMITTED WITH THE
 SEPARATE GAS PLANS.
  
 6) P1.1: PROVIDE A WATER RISER DRAWING SHOWING THE NEW
 WATER SUPPLY LINES TO THE REFRIGERATOR AND POT FILLER-
 SECTION 107.3.5.3 WPB. SHOW ON THE RISER THE POINTS OF
 CONNECTIONS FOR NEW DISTRIBUTION LINES FROM THE WATER
 HEATER, AND THE LOCATIONS OF REQUIRED WATER HAMMER
 ARRESTORS AND BACKFLOW PREVENTERS FOR THE NEW SUPPLY
 LINES- SECTIONS P2902.3 & P2903.5 FBC RES.
  
 7) P1.1: INDICATE THE HOT WATER PIPING WILL BE
 INSULATED WITH MINIMUM R3 PIPE INSULATION- SECTION
 R403.5.3 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  