2020-10-28 16:04:35RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
  
 NOTE: SEC. 801.3 FBC-EXISTING BUILDING. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE.
  
 1-SHEET S1.1: GARAGE FLOOR PLAN:
 A)PROVIDE COMPLETE OPENING FRAMING DETAIL FOR NEW
 OVERHEAD GARAGE DOOR AND NEW FRENCH DOORS IN THE GUEST
 SUITE. HEADER DETAIL ON SAME SHEET IS INCOMPLETE. IT
 DOESN'T SPECIFY ALL FRAMING MEMBERS SIZES AND
 CONNECTORS. PROVIDE COMPLETE INFORMATION. SEC. 504 AND
 SEC. 506 FBC-EXISTING BUILDING. SEC. R601.2
 FBC-RESIDENTIAL.
  
 B) PROVIDE INFILL FRAMING DETAIL FOR EXTERIOR WALL
 OPENINGS TO BE CLOSED.
 SPECIFY ALL FRAMING MEMBERS SIZES AND CONNECTORS,
 SHEATHING, INSULATION, FINISHES, ETC. SEC. 504 AND SEC.
 506 FBC-EXISTING BUILDING. SEC. R601.2 FBC-RESIDENTIAL.
  
 2- REQUIRED HEATING. SEC. R303.10 FBC-RESIDENTIAL.
 SPECIFY HOW PROVIDING HEAT TO THE NEW GUEST SUITE.
 SEC. 504 AND SEC. 506 FBC-EXISTING BUILDING.
  
 3- PLEASE SUBMIT A SEPARATE PERMIT APPLICATION FOR THE
 SEPARATE GARAGE/GUEST SUITE BUILDING. SAME PLANS CAN BE
 USED. SEPARATE PERMIT APPLICATIONS HELP TO COORDINATE
 INSPECTIONS FOR EACH BUILDING AND TO FACILITATE RECORDS
 RETENTION. SEC. 107.2.1.3 CITY AMENDMENTS.
 NOTE: PLEASE CONTACT ME TO EXPLAIN THIS. I CAN MAKE A
 COPY OF THE PERMIT APPLICATION TO GENERATE A NEW PERMIT
 NUMBER.
 THE IMPORTANT ISSUE OVER HERE IS FOR CONTRACTOR TO BE
 AWARE THAT THERE IS A SEPARATE PERMIT NUMBER FOR EACH
 STRUCTURE. THIS IS IMPORTANT WHEN CALLING FOR
 INSPECTIONS.
  
 4- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)PVC DOUBLE HUNG WINDOWS NOA 17-0630.10 SUBMITTED
 EXPIRED ON SEPTEMBER 17,2020. NEED CURRENT PRODUCT
 APPROVAL.
  
 B)OVERHEAD GARAGE DOOR.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS
 NOTE: COORDINATE ALSO WITH DOOR SCHEDULE ON SHEET A1.1.
 NOA'S TO MATCH NOA'S SUBMITTED TO AVOID
 CONFLICTS/DELAYS.
  
 6- SCOPE OF WORK IS NOT CLEAR.
 ARE ALL THE WINDOWS AND ALL EXTERIOR DOORS GOING TO BE
 REPLACED OR NOT. FLOOR PLANS ON SHEET A1.1 SHOW THEM AS
 EXISTING (EX.) AND THERE IS NO INDICATION THAT THESE
 DOORS/WINDOWS ARE GOING TO BE REPLACED. BUT, ON THE
 OTHER HAND THERE ARE WINDOWS AND DOORS SKETCHES AND
 SCHEDULES SUBMITTED UNDER THE SUPPORTING DOCUMENTS.
 PLEASE CLARIFY/REVISE AS REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved