| Plan Review Notes For Permit 20100498 |
| Permit Number |
20100498 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-10-16 09:08:07 | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | FBC B 107.2.1: | | | | | | 1) THE COVER PAGE A0.0 & DEMO PLAN PAGE A0.3, INDICATE | | | THAT THIS PLAN COVERS STAIR DEMO WORK WITH A NOTE | | | REFERRING TO SEPARATE PERMITS FOR STAIRS. THE OTHER | | | PERMIT APPLICATIONS, (# 19061180 & 20100658), THAT | | | INCLUDE STAIR DEMOLITION WORK HAVE NOT BEEN APPROVED. | | | PLEASE REMOVE STAIRS FROM THE WORK AREAS ON THIS PLAN | | | (PAGES A0.0 & A0.3). | | | | | | 2) IF THE INTENT IS TO INCLUDE STAIR DEMOLITION ON THIS | | | PLAN TO BE USED IN CONJUNCTION WITH THE OTHER PERMITS, | | | 20100658 WILL HAVE TO BE APPROVED AND 19061180 WILL | | | HAVE TO BE CLOSED. IN ANY CASE THE THRESHOLD/SPECIAL | | | INSPECTOR AGREEMENT NEEDS TO BE COMPLETED TO INCLUDE | | | THE CONTRACTOR(FAST TRAC) IN THE AGREEMENT. | | | | | | 3) A PROCEDURE SHOWING HOW THE PATRONS OF THE BUILDING | | | WILL BE DIRECTED TO AN ALTERNATE EGRESS WHILE THE STAIR | | | DEMOLITION AND WORK IS TAKING PLACE IS REQUIRED. |
|