| 2020-12-04 14:18:37 | CODES IN EFFECT |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | SAME COMMENTS AS FIRST REVIEW. NONE OF THEM HAVE BEEN |
| | ADDRESSED. |
| | |
| | 1) PLEASE PROVIDE ELECTRICAL DRAWINGS SHOWING THE |
| | FOLLOWING COMPONENTS OF THE ELECTRICAL DISTRIBUTION |
| | SYSTEM AS THEY APPLY TO THIS PROJECT. FBC 107.2 |
| | |
| | 2) ELECTRICAL FLOOR PLAN SHOWING THE LOCATION OF ALL |
| | NEW ELECTRICAL EQUIPMENT, LIGHTING FIXTURES, |
| | RECEPTACLES, HOME RUNS TO THE PANELS, EXISTING AND NEW |
| | PANELBOARDS, SYMBOLS. FBC 107.2 |
| | POWER RISER DIAGRAM (CAN BE PARTIAL), INCLUDING |
| | EXISTING AND NEW PANELBOARDS, FEEDER AND CONDUIT SIZES, |
| | GROUND CONDUCTORS, DISCONNECTING MEANS, TRANSFORMERS |
| | AFFECTED BY THIS WORK. FBC 107.2 |
| | LOAD CALCULATIONS OF AFFECTED PANELBOARDS SHOWING |
| | EXISTING AND NEW LOADS (NEC 220, NEC 220.87) |
| | PANEL SCHEDULES OF ALL AFFECTED PANELBOARDS SHOWING NEW |
| | AND EXISTING CIRCUITS, OVERCURRENT DEVICES, CONDUCTOR |
| | SIZES, RATING OF PANELBOARDS. FBC 107.2 |
| | |
| | ENRIQUE QUINONEZ |
| | ELECTRICAL PLANS EXAMINER |
| | [email protected] |
| | 561-805-6746 |
| | |