| 2020-10-27 14:08:49 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20100483 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE PERMIT APPLICATION INDICATES THERE ARE 2 HOODS |
| | BEING INSTALLED. THE DRAWINGS AND SPEC SHEETS ONLY SHOW |
| | HOOD 1. PLEASE BE CONSISTENT, IS THERE ONLY 1 HOOD OR |
| | IS THERE 2? FBC 107.2 |
| | |
| | 2) PLEASE PROVIDE A COMPLETE CODE ANALYSIS FOR THIS |
| | TENANT SPACE. IS THIS A CHANGE OF USE? BFC 107.2 |
| | |
| | 3) PLEASE PROVIDE A COMPLETE FLOOR PLAN FOR THE TENANT |
| | SPACE. FBC 107.2 |
| | |
| | 4) IS THERE A MASTER PERMIT FOR THIS PROJECT? |
| | |
| | 5) PLEASE SHOW THAT THE MAKE UP AIR FOR THE HOOD MEETS |
| | FBC M 508.1 FOR MAKE UP AIR AND FBC M 508.1.1 FOR MAKE |
| | UP AIR TEMPERATURE. |
| | |
| | 6) PLEASE PROVIDE THE DESIGN SCHEDULE OR DIAGRAM |
| | INDICATING THE DESIGN OUTDOOR AIR BALANCE FOR THIS |
| | FACILITY. FBC M 508.1.2 |
| | |
| | 7) PLEASE PROVIDE A ROOF DRAWING SHOWING THE HOOD |
| | EXHAUST OUTLET MEETS FBC M 501.3.1 |
| | |
| | 8) PLEASE SHOW ON THE ROOF DRAWING THE LOCATION OF THE |
| | MAKEUP AIR UNIT AND THAT IT MEETS FBC M 401.4 |
| | |
| | 9) PLEASE SHOW THAT THE HOOD TERMINATION AND MAKE UP |
| | AIR UNITS WILL MEET FBC M 304.11 |
| | |
| | 10) PLEASE SHOW THAT THE EQUIPMENT ON THE ROOF HAS |
| | MEANS OF ACCESS. FBC M 306.5 |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |