| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW STATUS: DENIED. |
| | |
| | 1) PLEASE PROVIDE ELECTRICAL DRAWINGS FOR THIS SPACE. |
| | INCLUDE FLOOR LAYOUT INDICATING THE LOCATION OF NEW AND |
| | EXISTING PANELS, LOCATION OF NEW EQUIPMENT, |
| | DISCONNECTING MEANS, HOME RUNS TO PANELBOARDS AND ANY |
| | OTHER NEW EQUIPMENT SUCH AS RECEPTACLES, AND LIGHTING |
| | FIXTURES. |
| | |
| | 2) PLEASE PROVIDE A BASIC POWER RISER DIAGRAM |
| | INDICATING ALL THE PANELBOARDS SERVING THIS TENANT-- |
| | EITHER INSTALLED NEW OR EXISTING. INCLUDE RATINGS OF |
| | PANELBOARDS, DISCONNECTING MEANS. INCLUDE THE SIZE AND |
| | TYPES OF THE FEEDERS TO THESE PANELBOARDS, INCLUDING |
| | SIZE AND TYPE OF CONDUITS, AND GROUND WIRES. |
| | |
| | 3) PLEASE PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR |
| | ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| | CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| | TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, |
| | 215.5, 408.4; FBC 107.3.5 |
| | |
| | 4) PLEASE PROVIDE LOAD CALCULATIONS FOR ALL PANELBOARDS |
| | AFFECTED BY THIS PROJECT. INCLUDE NEW AND EXISTING |
| | LOADS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |