| 2020-10-26 10:58:09 | 10/26/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A |
| | VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A |
| | LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS |
| | PER THE 2017 FBC- ENERGY- SEC. R 403.10.3. THIS MAY BE |
| | PUT IN ON PLANS BY THE ENGINEER OR IT WILL BE NOTED ON |
| | PLANS BY THE EXAMINER. |
| | |
| | 2. PLEASE SIZE RETURN ON THE PIPING FOR 1 1/2 PAGE ONE |
| | PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 3. PLEASE PROVIDE A SPECIFICATION FOR HEATERS AND SHOW |
| | THAT THE MINIMUM THERMAL EFFICIENCY OF 82 % FOR |
| | HEATERS, WHEN TESTED IN ACCORDANCE WITH ANSI Z 21.56. |
| | |
| | 4. THE DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM |
| | FLOW DOES NOT SHOW ALL FRICTION LOSS THROUGH THE |
| | COMPONENTS ON THE HEATER PER THE WPB AMENDMENTS TO THE |
| | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 5. PLEASE IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| | SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL WITH |
| | A LINE GRAPH. THIS IS NEEDED TO CONFIRM THE MAXIMUM |
| | SYSTEM FLOW FROM THE TDH CALCULATIONS PER THE |
| | ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. |
| | |
| | 6. PLEASE PROVIDE ALL MANUFACTURES SPECIFICATION FOR |
| | ALL SYSTEM COMPONENTS (HEATER, PUMP, CARTRIDGE FILTER, |
| | AND SALT SYS.) THAT ARE USED IN THE POOL PER THE WPB |
| | AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |