| 2020-10-29 09:09:25 | REPLACE ROOF FRAMING |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected]. |
| | CODE USED FOR REVIEW - 2017 FBC WITH WPB CHAPTER 1 |
| | AMENDMENTS |
| | |
| | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| | 1) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND |
| | DOORS (FRONT PAGES AND THE INSTALLATION INSTRUCTIONS). |
| | 2) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE |
| | ENGINEER. |
| | 3) PLEASE SHOW THE ATTIC ACCESS SIZE AND LOCATION TO |
| | COMPLY WITH FBC R807 |
| | 4) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE |
| | PRODUCT APPROVALS FOR THE ROOFING TILE (FRONT PAGES AND |
| | THE INSTALLATION INSTRUCTIONS). |
| | 5) PLEASE SHOW THE CONTINUED USE OF THE ROOM BESIDE THE |
| | GARAGE AS STORAGE AS SHOWN ON THE PALM BEACH COUNTY |
| | PROPERTY APPRAISER. |
| | 6) TRUSS LAYOUT AND ENGINEERING NEED TO BE SIGNED AND |
| | SEALED BY THE TRUSS DESIGNER. |
| | |
| | FYI = SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO |
| | BE DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR |
| | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW- OR - IF |
| | YOUR ARCHITECT OR ENGINEER DOES NOT HAVE AN ELECTRONIC |
| | OR DIGITAL SIGNATURE - PLEASE DROP OFF (CITY HALL DROP |
| | BOX) THE ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS |
| | ALONG WITH A "PLAN REVIEW REQUEST FORM" EXPLAINING THE |
| | REASON FOR SUBMITTING THE DOCUMENT OR DRAWINGS. PLAN |
| | REVIEW REQUEST FORM CAN BE OBTAINED BY E MAILING |
| | [email protected] AND ASKING FOR THE FORM. |