| 2020-10-19 18:55:59 | 10/19/20 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS | | | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | | | 1. PLEASE SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | CARTRIDGE FILTER AND THE PUMP PER THE WPB AMENDMENTS TO | | | FBC SEC. 107.2.1. | | | | | | 2. PLEASE SUBMIT POOL PUMP CURVE AND IDENTIFY ON THE | | | PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE PUMP | | | BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO CONFIRM | | | THE MAXIMUM SYSTEM FLOW FROM THE TDH CALCULATIONS PER | | | THE ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | LUIS A. CRESPO | | | PLUMBING PLAN EXAMINER / INSPECTOR | | | EMAIL: [email protected] OFFICE: 561 805-6720 | | | |
|