| 2020-10-26 12:16:39 | 1ST REVIEW FBC-2017 RES. FUEL GAS |
| | PERMIT- 20100418 |
| | 10/26/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE GENERATOR SPECS SUBMITTED UNDER PERMIT- 20100300 |
| | INDICATE A FULL LP GAS LOAD OF 355,000 BTU'S- PLEASE |
| | CORRECT THE INCORRECT LOAD ON THE RISER- SECTION |
| | 107.2.1 WPB. |
| | |
| | 2) THE LP TANK INSTALLATION DETAIL IS NOT LEGIBLE. |
| | PLEASE PROVIDE CLEAR DETAILS THAT INCLUDE- |
| | A) ENGINEERING FOR ANCHORING THE TANK TO PREVENT |
| | FLOTATION, COLLAPSE, OR LATERAL MOVEMENT- SECTION |
| | 6.6.1.6 NFPA 58- 14. PLEASE INCLUDE A FRONT AND SIDE |
| | ELEVATION VIEW THAT SHOWS THE BURIAL DEPTH, ANCHORING |
| | BASE MATERIAL, AND THE TYPES, SIZES, AND NUMBERS OF |
| | ANCHORS, CABLES OR STRAPS, AND THE TYPE OF PROTECTIVE |
| | SLEEVES FOR THE CABLES OR STRAPS |
| | B) SHOW HOW THE TANK WILL BE PROTECTED AGAINST |
| | CORROSION BY INSTALLATION OF A CATHODIC PROTECTION |
| | SYSTEM CONSISTING OF A SACRIFICIAL ANODE OR AN |
| | IMPRESSED CURRENT ANODE PER SECTIONS 5.2.1.11 & |
| | 6.6.6.1(I) NFPA 58. INDICATE THE TYPE OF PROTECTION AND |
| | HOW IT WILL BE TESTED- SECTION 6.17.1. |
| | |
| | 3) THE CONTRACTOR OR QUALIFIER WHO PREPARED THE DRAWING |
| | SHALL PROVIDE HIS/HER SIGNATURE ON IT- SECTION 107.2.1 |
| | WPB, AND FLORIDA STATUTES 471.003(2)(H) & 471.025. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |